Modbus Parameter Specifications

Table Of Contents
MODBUS ACE V1.00
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 10/6/2003 ·File: ext001931381.docx ·Last printed 9/30/2019 10:29:00
AM ·Page 65 of 78
Form 1003
Example:
Holding register address Content
D400 D011 (motor status)
D401 D010 (actual speed)
D402 D019 (current modulation level)
D403 D021 (current power)
With read access to the input register D100, the motor status is obtained.
With read access to the input register D101, the actual speed is obtained.
The same applies accordingly to the following input registers.
With joint read access to the input registers D100 - D103, the content of the input registers Motor status,
Actual speed, Current modulation level and Current power is obtained with a single command.
2.51.1 Original addresses of mirrored input registers
Address : D400 - D40F
Write authorization : ebm-papst, customer
Coding:

The addresses of the input registers that are mirrored in the input register range D100 - D10F are defined
here. See above for further information on the function.
2.52 Mass flow calculation
2.52.1 Elevation above sea level
Address : D602
Write authorization : ebm-papst, customer, end customer
This parameter describes the absolute elevation of a fan with respect to mean sea level. This parameter is
used to determine the density of the transported air, which in turn is needed to calculate the mass flow.
Coding:


The data bytes are classified as signed 16-bit integers.