Modbus Parameter Specifications

Table Of Contents
MODBUS ACE V1.00
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 10/6/2003 ·File: ext001931381.docx ·Last printed 9/30/2019 10:29:00
AM ·Page 56 of 78
Form 1003
2.41 Enable source
Address : D16A
Write authorization : ebm-papst, customer, end customer
Coding:
Value
Enable function by...
0
Inactive
1
"Enable RS485" parameter
The MSB has no significance.
Permissible value range: 0..1
Function:
The Enable signal has two states (enabled / disabled)
The fan can only be started in "enabled" state.
In "disabled" state the fan is stationary irrespective of any set value specification.
All errors are reset on transition from "enabled" to "disabled" state
This action corresponds to setting of the "Error" bit in the parameter Reset
2.42 Stored enable RS485
Address : D16B
Write authorization : ebm-papst, customer, end customer
If the "Store set value" function (holding register D103) is active, the value of the parameter "Enable RS485"
(holding register D00F) is copied to the "Stored enable RS485" parameter holding register after a break in the
power supply.
Once the power supply has been restored, the value of the parameter "Stored enable RS485" is copied into
the parameter "Enable RS485"
As the parameter Enable RS485 is located in the volatile memory, this value (if applicable) has to be saved in
the non-volatile memory as well to permit retention of the existing state following interruption and restoration of
the power supply. The parameter "Stored enable RS485" is intended for this purpose.
Coding:
Value
Enable
0
Off (no enable)
1
On (enable)
Permissible value range: 0..1