2.37 Set value for fail safe function
Address : D15D
Write authorization : ebm-papst, customer
If a break in the set value source (holding register D101) is detected, the fan automatically switches to the set
value for fail safe function specified here, if fail-safe set value source (holding register D15C) = 1.
Coding:
Notes: The coding corresponds to the coding for the set value.
2.38 Time lag fail-safe speed
Address : D15E
Write authorization : ebm-papst, customer
Only for Set value source (holding register D101) through RS485 (1):
If no command is issued to the fan for the time specified here, the fan automatically switches to the selected
Fail-safe speed set value source (holding register D15C).
Coding:
msData bytesmslagsafe time Fail 100