2.22 Starting modulation level
Address : D116
Write authorization : ebm-papst
The starting modulation level specifies the modulation level with which the motor is started after a start
command.
Coding:

󰇛󰇜



Starting modulation level in percent
The motor always starts with the starting modulation level.
A high starting modulation level results in a high current on starting the motor.
The MSB has no significance.
2.23 Maximum permissible modulation level
Address : D117
Write authorization : ebm-papst
This parameter forms the upper limit for the maximum modulation level (holding register D10E).
Coding:

󰇛󰇜



Maximum permissible modulation level in percent
The MSB has no significance.
2.24 Minimum permissible modulation level
Address : D118
Write authorization : ebm-papst
This parameter forms the lower limit for the minimum modulation level.
Coding:

󰇛󰇜



Minimum permissible modulation level in percent
If the setting selected for this value is too low (in particular values < 5%), the motor may cut out with the error
"Motor blocked".
The MSB has no significance