2.19 Maximum modulation level
Address : D10E
Write authorization : ebm-papst, customer
Coding:

󰇛󰇜



Maximum modulation level in percent
Limitation:
8% < Maximum modulation level < Maximum permissible modulation level (holding register D117)
The MSB has no significance
2.20 Minimum modulation level
Address : D110
Write authorization : ebm-papst, customer, end customer
Coding:

󰇛󰇜



Minimum modulation level in percent
Limitation:
Minimum modulation level > Minimum permissible modulation level (holding register D118)
The MSB has no significance
2.21 Motor stop enable
Parameter set 1 address : D112
Write authorization : ebm-papst, customer, end customer
Coding:
Value
Motor stop
0
Motor always runs (even with set value = 0)
1
Motor stops with set value = 0
The MSB has no significance.