2.12 Fan address
Address : D100
Write authorization : ebm-papst, customer, end customer
Coding:

󰇛

󰇜
The MSB has no significance.
Permissible value range: 1 to 247
If the permitted range is not maintained, the fan takes on the address 1.
2.13 Set value source
Address : D101
Write authorization : ebm-papst, customer, end customer
This parameter specifies where the set value requirement comes from.
Coding:
Value
Set value source
0
Analog input Ain1
1
RS485 (Set value parameter, holding register D001)
The MSB has no significance.
Permissible value range: 0..1