LM24A SR
1
Technical data sheet Damper actuator LM24A-SR
Technische Daten
Electrical data
Nominal voltage AC 24 V, 50/60 Hz
DC 24 V
Nominal voltage range AC/DC 19.2 ... 28.8 V
Power consumption In operation
At rest
For wire sizing
1 W @ nominal torque
0.4 W
2 VA
Connection Cable 1 m, 4 x 0.75 mm
2
Functional data Torque (nominal torque) Min. 5 Nm @ nominal voltage
Control Control signal Y
Working range
DC 0 ... 10 V, typical input impedance 100 kΩ
DC 2 ... 10 V
Position feedback (Measuring voltage) DC 2 ... 10 V, max. 1 mA
Position accuracy ±5%
Direction of rotation Reversible with switch 0 / 1
Direction of rotation at Y = 0 V at switch position 0
resp. 1
Manual override Gearing latch disengaged with pushbutton,
self-resetting
Angle of rotation
Max. 95°
,
limited on both sides
by means of adjustable, mechanical end stops
Running time 150 s
Sound power level Max. 35 dB (A)
Position indication Mechanical, pluggable
Safety
Protection class III Safety extra-low voltage
Degree of protection IP54 in any mounting position
EMC CE according to 89/336/EEC
Mode of operation Type 1 (to EN 60730-1)
Ambient temperature range –30 ... +50°C
Non-operating temperature –40 ... +80°C
Ambient humidity range 95% r.H., non-condensating (EN 60730-1)
Maintenance Maintenance-free
Dimensions / Weight
Dimensions See «Dimensions» on page 2
Weight Approx. 500 g
Damper actuator for operating
air control dampers in ventilation
and air-conditioning systems for
building services installations
• For air control dampers up to
approx. 1 m
2
• Torque 5 Nm
• Nominal voltage AC/DC 24 V
• Control: modulating DC 0 ... 10 V,
position feedback DC 2 ... 10 V
Safety notes
!
• The damper actuator is not allowed to be used outside the specified field of applica
tion,
especially in aircraft or any other form of air transport.
• Assembly must be carried out by trained personnel. Any legal regulations or regulations
issued by authorities must be observed during assembly.
• The device may only be opened at the manufacturer‘s site. It does not contain any parts
that can be replaced or repaired by the user.
• The cable must not be removed from the device.
• When calculating the required torque, the specifications supplied by the damper
manufacturers (cross section, design, installation site), and the air flow conditions must
be observed.
• The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.