MODBUS LITE V5.01 parameter specification
Table Of Contents
- 1 Frame protocol
 - 2 Holding Register
- 2.1 Overview
 - 2.2 Reset
 - 2.3 Default set value
 - 2.4 Password
 - 2.5 Control default setting
 - 2.6 Control customer setting
 - 2.7 Operating hours counter
 - 2.8 Operating minutes counter
 - 2.9 Fan address
 - 2.10 Source set value
 - 2.11 Preferred running direction
 - 2.12 Save set value
 - 2.13 Internal parameter set
 - 2.14 Control mode
 - 2.15 Control parameters
 - 2.16 Maximum modulation level
 - 2.17 Minimum modulation level
 - 2.18 Enable motor stop
 - 2.19 Set value (EEPROM)
 - 2.20 Starting modulation level
 - 2.21 Maximum permissible modulation level
 - 2.22 Minimum permissible modulation level
 - 2.23 Maximum speed
 - 2.24 Maximum permissible speed
 - 2.25 Ramp-up curve / ramp-down curve
 - 2.26 Limit speed
 - 2.27 Potentiometer characteristic
 - 2.28 Control limitation
 - 2.29 Maximum power
 - 2.30 Maximum coil current
 - 2.31 Limiting speed for running monitor
 - 2.32 Interface settings
 - 2.33 Shedding function
 - 2.34 Relay dropout delay
 - 2.35 Fail safe function on/off
 - 2.36 Fail safe function set value
 - 2.37 Fail safe function time lag
 - 2.38 Fail safe function running direction
 - 2.39 Potentiometer characteristic limiting value for cable break
 - 2.40 Sensor
 - 2.41 Customer data
 - 2.42 Error history
 - 2.43 Reference value of DC-link voltage
 - 2.44 Reference value of DC-link current
 - 2.45 Production data
 
 - 3 Input Register
- 3.1 Overview
 - 3.2 Identification
 - 3.3 Maximum number of bytes
 - 3.4 Software name of bus controller
 - 3.5 Software version of bus controller
 - 3.6 Software name of commutation controller
 - 3.7 Software version of commutation controller
 - 3.8 Actual speed
 - 3.9 Motor status
 - 3.10 Warning
 - 3.11 DC-link voltage
 - 3.12 DC-link current
 - 3.13 Module temperature
 - 3.14 Motor temperature
 - 3.15 Interior electronics temperature
 - 3.16 Current direction of rotation
 - 3.17 Current modulation level
 - 3.18 Current set value
 - 3.19 Sensor actual values
 - 3.20 Current parameter set
 - 3.21 Current power
 
 
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200" 
_______________________________________________________________________________________ 
ebm-papst Mulfingen GmbH & Co. KG 
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com 
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00 
·Page 33 of 70 
Form 1003 
2.10  Source set value 
Address    : D101 
Write authorisation  : ebm-papst, customer, end customer 
Encoding: 
This parameter specifies the source from which the set value is taken: 
Value 
Source set value 
0 
Analogue input 0 to 10 V 
1 
RS485 (default set value parameter D001) 
The MSB is of no relevance! 
Permitted value range: 0 to 1 
2.11  Preferred running direction 
Address    : D102 
Write authorisation  : ebm-papst, customer, end customer 
Encoding: 
This parameter specifies the preferred running direction. 
Value 
Preferred running direction 
0 
anti-clockwise 
1 
clockwise 
The MSB is of no relevance! 
Permitted value range: 0 to 1 
After this parameter is written, the new value becomes applicable immediately (no reset necessary). 
If the fail safe function is activated and a break in the MODBUS connection is detected, the direction of 
rotation is set to the value of "Fail safe function running direction" (see 2.38). The parameter Preferred running 
direction is not relevant then. 