Drive P2K2 P3K0 P3K7 P5K5 P7K5 P11K P15K
Continuous (3x551–600 V) [A] 2.7 3.4 4.3 6.3 7.7 12.6 15.4
Intermittent (3x551–600 V) [A] 3.0 3.7 4.7 6.9 8.5 13.9 16.9
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
MyDrive® ecoSmart
TM
website.
2
Efficiency measured at nominal current. For energy efficiency class, see 6.4.13 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoSmart
TM
website.
Table 27: 3x525–600 V AC, 18.5–90 kW (25–125 hp), Enclosure Sizes H6–H8
Drive P18K P22K P30K P37K P45K P55K P75K P90K
Typical shaft output [kW] 18.5 22.0 30.0 37 45.0 55.0 75.0 90.0
Typical shaft output [hp] 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.0
Protection rating IP20 H6 H6 H6 H7 H7 H7 H8 H8
Maximum cable size in termi-
nals (mains, motor) [mm
2
(AWG)]
35 (2) 35 (2) 35 (2) 50 (1) 50 (1) 50 (1) 95 (0) 120 (4/0)
Output current - 40°C (104°F) ambient temperature
Continuous (3x525–550 V) [A] 28.0 36.0 43.0 54.0 65.0 87.0 105.0 137.0
Intermittent (3x525–550 V) [A] 30.8 39.6 47.3 59.4 71.5 95.7 115.5 150.7
Continuous (3x551–600 V) [A] 27.0 34.0 41.0 52.0 62.0 83.0 100.0 131.0
Intermittent (3x551–600 V) [A] 29.7 37.4 45.1 57.2 68.2 91.3 110.0 144.1
Maximum input current
Continuous (3x525–550 V) [A] 27.0 33.1 45.1 54.7 66.5 81.3 109.0 130.9
Intermittent (3x525–550 V) [A] 29.7 36.4 49.6 60.1 73.1 89.4 119.9 143.9
Continuous (3x551–600 V) [A] 25.7 31.5 42.9 52.0 63.3 77.4 103.8 124.5
Intermittent (3x551–600 V) [A] 28.3 34.6 47.2 57.2 69.6 85.1 114.2 137.0
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], best
case/typical
(1)
385 458 542 597 727 1092 1380 1658
Weight enclosure protection
rating IP54 [kg (lb)]
24.5 (54) 24.5 (54) 24.5 (54) 36.0
(79.3)
36.0
(79.3)
36.0
(79.3)
51.0
(112.4)
51.0
(112.4)
Efficiency [%], best case/typical
(2)
98.4 98.4 98.5 98.5 98.7 98.5 98.5 98.5
Output current - 50°C (122°F) ambient temperature
Continuous (3x525–550 V) [A] 19.6 25.2 30.1 37.8 45.5 60.9 73.5 95.9
Intermittent (3x525–550 V) [A] 21.6 27.7 33.1 41.6 50.0 67.0 80.9 105.5
Continuous (3x551–600 V) [A] 18.9 23.8 28.7 36.4 43.3 58.1 70.0 91.7
Intermittent (3x551–600 V) [A] 20.8 26.2 31.6 40.0 47.7 63.9 77.0 100.9
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
72 | Danfoss A/S © 2019.11