Manual
Table Of Contents
- VLT® HVAC Basic Drive FC 101
- English US
- Contents
- Introduction
- Safety
- Installation
- Mechanical Installation
- Electrical Installation
- Electrical Installation in General
- IT Mains
- Mains and Motor Connection
- Introduction
- Connecting to Mains and Motor
- Relays and Terminals on Enclosure Sizes H1–H5
- Relays and Terminals on Enclosure Size H6
- Relays and Terminals on Enclosure Size H7
- Relays and Terminals on Enclosure Size H8
- Connecting to Mains and Motor for Enclosure Size H9
- Relays and Terminals on Enclosure Size H10
- Enclosure Size I2
- Enclosure Size I3
- Enclosure Size I4
- IP54 Enclosure Sizes I2, I3, I4
- Enclosure size I6
- Enclosure size I7, I8
- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
Drive PK75 P1K5 P2K2 P3K0 P4KO P5K5 P7K5 P11K P15K P18K
Weight enclosure protection
rating IP54 [kg (lb)]
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
7.2
(15.9)
7.2
(15.9)
13.8
(30.4)
13.8
(30.4)
13.8
(30.4)
Efficiency [%], best case/typical
(2)
98.0/9
7.6
97.7/9
7.2
98.3/9
7.9
98.2/9
7.8
98.0/9
7.6
98.4/9
8.0
98.2/9
7.8
98.1/9
7.9
98.0/9
7.8
98.1/9
7.9
Output current - 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A] 1.93 3.7 4.85 6.3 7.5 10.9 14.0 20.9 28.0 33.0
Intermittent (3x380–440 V) [A] 2.1 4.07 5.4 6.9 9.2 12.0 15.4 23.0 30.8 36.3
Continuous (3x441–480 V) [A] 1.8 3.4 4.4 5.5 6.8 10.0 12.6 19.1 24.0 30.0
Intermittent (3x441–480 V) [A] 2.0 3.7 4.8 6.1 8.3 11.0 13.9 21.0 26.4 33.0
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmart
TM
website.
2
Efficiency measured at nominal current. For energy efficiency class, see 6.4.13 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoSmart
TM
website.
Table 25: 3x380–480 V AC, 22–90 kW (30–125 hp), Enclosure Sizes I6–I8
Drive P22K P30K P37K P45K P55K P75K P90K
Typical shaft output [kW] 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output [hp] 30.0 40.0 50.0 60.0 70.0 100.0 125.0
Protection rating IP54 I6 I6 I6 I7 I7 I8 I8
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
35 (2) 35 (2) 35 (2) 50 (1) 50 (1) 95 (3/0) 120 (4/0)
Output current - 40°C (104°F) ambient temperature
Continuous (3x380–440 V) [A] 44.0 61.0 73.0 90.0 106.0 147.0 177.0
Intermittent (3x380–440 V) [A] 48.4 67.1 80.3 99.0 116.6 161.7 194.7
Continuous (3x441–480 V) [A] 40.0 52.0 65.0 80.0 105.0 130.0 160.0
Intermittent (3x441–480 V) [A] 44.0 57.2 71.5 88.0 115.5 143.0 176.0
Maximum input current
Continuous (3x380–440 V) [A] 41.8 57.0 70.3 84.2 102.9 140.3 165.6
Intermittent (3x380–440 V) [A] 46.0 62.7 77.4 92.6 113.1 154.3 182.2
Continuous (3x441–480 V) [A] 36.0 49.2 60.6 72.5 88.6 120.9 142.7
Intermittent (3x441–480 V) [A] 39.6 54.1 66.7 79.8 97.5 132.9 157.0
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], best
case/typical
(1)
496 734 995 840 1099 1520 1781
Weight enclosure protection rat-
ing IP54 [kg (lb)]
27 (59.5) 27 (59.5) 27 (59.5) 45 (99.2) 45 (99.2) 65 (143.3) 65 (143.3)
Efficiency [%], best case/typical
(2)
98.0 97.8 97.6 98.3 98.2 98.1 98.3
Output current - 50°C (122°F) ambient temperature
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078