Drive P18K P22K P30K P37K P45K P55K P75K P90K
Intermittent (3x441–480 V) [A] 32.2 38.1 54.1 66.7 79.8 97.5 132.9 157.0
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], best
case/typical
(1)
412/456 475/523 733 922 1067 1133 1733 2141
Weight enclosure protection
rating IP20 [kg (lb)]
9.5 (20.9) 9.5 (20.9) 24.5 (54) 24.5 (54) 24.5 (54) 36.0
(79.4)
36.0
(79.4)
51.0
(112.4)
Efficiency [%], best case/typical
(2)
98.1/97.9 98.1/97.9 97.8 97.7 98 98.2 97.8 97.9
Output current - 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A] 34.1 38.0 48.8 58.4 72.0 74.2 102.9 123.9
Intermittent (3x380–440 V) [A] 37.5 41.8 53.7 64.2 79.2 81.6 113.2 136.3
Continuous (3x441–480 V) [A] 31.3 35.0 41.6 52.0 64.0 73.5 91.0 112.0
Intermittent (3x441–480 V) [A] 34.4 38.5 45.8 57.2 70.4 80.9 100.1 123.2
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmart
TM
website.
2
Efficiency measured at nominal current. For energy efficiency class, see 6.4.13 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoSmart
TM
website.
Table 24: 3x380–480 V AC, 0.75–18.5 kW (1–25 hp), Enclosure Sizes I2–I4
Drive PK75 P1K5 P2K2 P3K0 P4KO P5K5 P7K5 P11K P15K P18K
Typical shaft output [kW] 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11 15 18.5
Typical shaft output [hp] 1.0 2.0 3.0 4.0 5.0 7.5 10.0 15 20 25
Protection rating IP54 I2 I2 I2 I2 I2 I3 I3 I4 I4 I4
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 16 (6) 16 (6) 16 (6)
Output current - 40°C (104°F) ambient temperature
Continuous (3x380–440 V) [A] 2.2 3.7 5.3 7.2 9.0 12.0 15.5 23.0 31.0 37.0
Intermittent (3x380–440 V) [A] 2.4 4.1 5.8 7.9 9.9 13.2 17.1 25.3 34.0 40.7
Continuous (3x441–480 V) [A] 2.1 3.4 4.8 6.3 8.2 11.0 14.0 21.0 27.0 34.0
Intermittent (3x441–480 V) [A] 2.3 3.7 5.3 6.9 9.0 12.1 15.4 23.1 29.7 37.4
Maximum input current
Continuous (3x380–440 V) [A] 2.1 3.5 4.7 6.3 8.3 11.2 15.1 22.1 29.9 35.2
Intermittent (3x380–440 V) [A] 2.3 3.9 5.2 6.9 9.1 12.3 16.6 24.3 32.9 38.7
Continuous (3x441–480 V) [A] 1.8 2.9 3.9 5.3 6.8 9.4 12.6 18.4 24.7 29.3
Intermittent (3x441–480 V) [A] 2.0 3.2 4.3 5.8 7.5 10.3 13.9 20.2 27.2 32.2
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], best
case/typical
(1)
21/16 46/57 46/58 66/83 95/11
8
104/1
31
159/1
98
248/2
74
353/3
79
412/4
56
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 69
Danfoss A/S © 2019.11