Manual
Table Of Contents
- VLT® HVAC Basic Drive FC 101
- English US
- Contents
- Introduction
- Safety
- Installation
- Mechanical Installation
- Electrical Installation
- Electrical Installation in General
- IT Mains
- Mains and Motor Connection
- Introduction
- Connecting to Mains and Motor
- Relays and Terminals on Enclosure Sizes H1–H5
- Relays and Terminals on Enclosure Size H6
- Relays and Terminals on Enclosure Size H7
- Relays and Terminals on Enclosure Size H8
- Connecting to Mains and Motor for Enclosure Size H9
- Relays and Terminals on Enclosure Size H10
- Enclosure Size I2
- Enclosure Size I3
- Enclosure Size I4
- IP54 Enclosure Sizes I2, I3, I4
- Enclosure size I6
- Enclosure size I7, I8
- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
Drive PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K
Continuous (3x380–440 V) [A] 1.2 2.1 3.5 4.7 6.3 8.3 11.2 15.1 22.1 29.9
Intermittent (3x380–440 V) [A] 1.3 2.3 3.9 5.2 6.9 9.1 12.3 16.6 24.3 32.9
Continuous (3x441–480 V) [A] 1.0 1.8 2.9 3.9 5.3 6.8 9.4 12.6 18.4 24.7
Intermittent (3x441–480 V) [A] 1.1 2.0 3.2 4.3 5.8 7.5 10.3 13.9 20.2 27.2
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], best
case/typical
(1)
13/15 16/21 46/57 46/58 66/83 95/11
8
104/1
31
159/1
98
248/2
74
353/3
79
Weight enclosure protection
rating IP20 [kg (lb)]
2.0
(4.4)
2.0
(4.4)
2.1
(4.6)
3.3
(7.3)
3.3
(7.3)
3.4
(7.5)
4.3
(9.5)
4.5
(9.9)
7.9
(17.4)
7.9
(17.4)
Efficiency [%], best case/typical
(2)
97.8/9
7.3
98.0/9
7.6
97.7/9
7.2
98.3/9
7.9
98.2/9
7.8
98.0/9
7.6
98.4/9
8.0
98.2/9
7.8
98.1/9
7.9
98.0/9
7.8
Output current - 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A] 1.04 1.93 3.7 4.85 6.3 8.4 10.9 14.0 20.9 28.0
Intermittent (3x380–440 V) [A] 1.1 2.1 4.07 5.4 6.9 9.2 12.0 15.4 23.0 30.8
Continuous (3x441–480 V) [A] 1.0 1.8 3.4 4.4 5.5 7.5 10.0 12.6 19.1 24.0
Intermittent (3x441–480 V) [A] 1.1 2.0 3.7 4.8 6.1 8.3 11.0 13.9 21.0 26.4
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmart
TM
website.
2
Typical: under rated condition. Best case: the optimal condition is adopt, such as the higher input voltage and lower switching frequency.
Table 23: 3x380–480 V AC, 18.5–90 kW (25–125 hp), Enclosure Sizes H5–H8
Drive P18K P22K P30K P37K P45K P55K P75K P90K
Typical shaft output [kW] 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output [hp] 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.0
Protection rating IP20 H5 H5 H6 H6 H6 H7 H7 H8
Maximum cable size in termi-
nals (mains, motor) [mm
2
(AWG)]
16 (6) 16 (6) 35 (2) 35 (2) 35 (2) 50 (1) 95 (0) 120
(250MC
M)
Output current-40°C (104°F) ambient temperature
Continuous (3x380–440 V)[A] 37.0 42.5 61.0 73.0 90.0 106.0 147.0 177.0
Intermittent (3x380–440 V) [A] 40.7 46.8 67.1 80.3 99.0 116.0 161.0 194.0
Continuous (3x441–480 V) [A] 34.0 40.0 52.0 65.0 80.0 105.0 130.0 160.0
Intermittent (3x441–480 V) [A] 37.4 44.0 57.2 71.5 88.0 115.0 143.0 176.0
Maximum input current
Continuous (3x380–440 V) [A] 35.2 41.5 57.0 70.0 84.0 103.0 140.0 166.0
Intermittent (3x380–440 V) [A] 38.7 45.7 62.7 77.0 92.4 113.0 154.0 182.0
Continuous (3x441–480 V) [A] 29.3 34.6 49.2 60.6 72.5 88.6 120.9 142.7
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
68 | Danfoss A/S © 2019.11