Drive P11K P15K P18K P22K P30K P37K P45K
Maximum cable size in terminals
(mains, motor) [m
2
(AWG)]
16 (6) 35 (2) 35 (2) 50 (1) 50 (1) 95 (0) 120 (4/0)
Output current - 40°C (104°F) ambient temperature
Continuous (3x200–240 V) [A] 42.0 59.4 74.8 88.0 115.0 143.0 170.0
Intermittent (3x200–240 V) [A] 46.2 65.3 82.3 96.8 126.5 157.3 187.0
Maximum input current
Continuous 3x200–240 V) [A] 41.0/38.2 52.7 65.0 76.0 103.7 127.9 153.0
Intermittent (3x200–240V) [A] 45.1/42.0 58.0 71.5 83.7 114.1 140.7 168.3
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], Best
case/typical
(1)
369/386 512 697 879 1149 1390 1500
Weight enclosure protection rat-
ing IP20 [kg (lb)]
9.5 (20.9) 24.5 (54) 24.5 (54) 36.0 (79.4) 36.0 (79.4) 51.0
(112.4)
51.0
(112.4)
Efficiency [%], best case/typical
(2)
97.2/97.1 97.0 97.1 96.8 97.1 97.1 97.3
Output current - 50°C (122°F) ambient temperature
Continuous (3x200–240 V) [A] 33.0 41.6 52.4 61.6 80.5 100.1 119
Intermittent (3x200–240 V) [A] 36.3 45.8 57.6 67.8 88.6 110.1 130.9
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmart
TM
website.
2
Efficiency measured at nominal current. For energy efficiency class, see 6.4.13 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoSmart
TM
website.
6.1.2 3x380–480 V AC
Table 22: 3x380–480 V AC, 0.37–15 kW (0.5–20 hp), Enclosure Sizes H1–H4
Drive PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K
Typical shaft output [kW] 0.37 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0
Typical shaft output [hp] 0.5 1.0 2.0 3.0 4.0 5.0 7.5 10.0 15.0 20.0
Protection rating IP20 H1 H1 H1 H2 H2 H2 H3 H3 H4 H4
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 16 (6) 16 (6)
Output current - 40°C (104°F) ambient temperature
Continuous (3x380–440 V)[A] 1.2 2.2 3.7 5.3 7.2 9.0 12.0 15.5 23.0 31.0
Intermittent (3x380–440 V) [A] 1.3 2.4 4.1 5.8 7.9 9.9 13.2 17.1 25.3 34.0
Continuous (3x441–480 V) [A] 1.1 2.1 3.4 4.8 6.3 8.2 11.0 14.0 21.0 27.0
Intermittent (3x441–480 V) [A] 1.2 2.3 3.7 5.3 6.9 9.0 12.1 15.4 23.1 29.7
Maximum input current
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 67
Danfoss A/S © 2019.11