Manual
Table Of Contents
- VLT® HVAC Basic Drive FC 101
- English US
- Contents
- Introduction
- Safety
- Installation
- Mechanical Installation
- Electrical Installation
- Electrical Installation in General
- IT Mains
- Mains and Motor Connection
- Introduction
- Connecting to Mains and Motor
- Relays and Terminals on Enclosure Sizes H1–H5
- Relays and Terminals on Enclosure Size H6
- Relays and Terminals on Enclosure Size H7
- Relays and Terminals on Enclosure Size H8
- Connecting to Mains and Motor for Enclosure Size H9
- Relays and Terminals on Enclosure Size H10
- Enclosure Size I2
- Enclosure Size I3
- Enclosure Size I4
- IP54 Enclosure Sizes I2, I3, I4
- Enclosure size I6
- Enclosure size I7, I8
- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
6 Specifications
6.1 Mains Supply
6.1.1 3x200–240 V AC
Table 20: 3x200–240 V AC, 0.25–7.5 kW (0.33–10 hp)
Drive PK25 PK37 PK75 P1K5 P2K2 P3K7 P5K5 P7K5
Typical shaft output [kW] 0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5
Typical shaft output [hp] 0.33 0.5 1.0 2.0 3.0 5.0 7.5 10.0
Protection rating IP20 H1 H1 H1 H1 H2 H3 H4 H4
Maximum cable size in termi-
nals (mains, motor) [m
2
(AWG)]
4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 16 (6) 16 (6)
Output current - 40°C (104°F) ambient temperature
Continuous (3x200–240 V) [A] 1.5 2.2 4.2 6.8 9.6 15.2 22.0 28.0
Intermittent (3x200–240 V) [A] 1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8
Maximum input current
Continuous 3x200–240 V) [A] 1.1 1.6 2.8 5.6 8.6/7.2 14.1/12.0 21.0/18.0 28.3/24.0
Intermittent (3x200–240V) [A] 1.2 1.8 3.1 6.2 9.5/7.9 15.5/13.2 23.1/19.8 31.1/26.4
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], Best
case/typical
(1)
12/14 15/18 21/26 48/60 80/102 97/120 182/204 229/268
Weight enclosure protection
rating IP20 [kg (lb)]
2.0 (4.4) 2.0 (4.4) 2.0 (4.4) 2.1 (4.6) 3.4 (7.5) 4.5 (9.9) 7.9 (17.4) 7.9 (17.4)
Efficiency [%], best case/typical
(2)
97.0/96.5 97.3/96.8 98.0/97.6 97.6/97.0 97.1/96.3 97.9/97.4 97.3/97.0 98.5/97.1
Output current - 50°C (122°F) ambient temperature
Continuous (3x200–240 V) [A] 1.5 1.9 3.5 6.8 9.6 13.0 19.8 23.0
Intermittent (3x200–240 V) [A] 1.7 2.1 3.9 7.5 10.6 14.3 21.8 25.3
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmart
TM
website.
2
Efficiency measured at nominal current. For energy efficiency class, see 6.4.13 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoSmart
TM
website.
Table 21: 3x200–240 V AC, 11–45 kW (15–60 hp)
Drive P11K P15K P18K P22K P30K P37K P45K
Typical shaft output [kW] 11.0 15.0 18.5 22.0 30.0 37.0 45.0
Typical shaft output [hp] 15.0 20.0 25.0 30.0 40.0 50.0 60.0
Protection rating IP20 H5 H6 H6 H7 H7 H8 H8
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
66 | Danfoss A/S © 2019.11