Manual

Table Of Contents
Fault
num‐
ber
Alarm/
warning
bit num‐
ber
Fault text Warn‐
ing
Alarm Trip
locked
Cause of problem
80 29 Drive initial-
ised
X All parameter settings are initialized to default settings.
87 47 Auto DC
Braking
X The drive is auto DC braking.
95 40 Broken Belt X X Torque is below the torque level set for no load, indicat-
ing a broken belt. See parameter group 22-6* Broken Belt
Detection.
126 Motor Rotat-
ing
X High back EMF voltage. Stop the rotor of the PM motor.
200 Fire Mode X Fire mode has been activated.
202 Fire Mode
Limits Excee-
ded
X Fire mode has suppressed 1 or more warranty voiding
alarms.
250 New spare-
part
X X The power or switch mode power supply has been ex-
changed (on 400 V, 30–90 kW (40–125 hp) and 600 V
units). Contact the local Danfoss supplier.
251 New Type-
code
X X The drive has a new type code (on 400 V, 30– 90 kW (40–
125 hp) and 600 V units). Contact the local Danfoss sup-
plier.
Warnings and Alarms
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 65
Danfoss A/S © 2019.11