47 23 24 V supply
low
X X X 24 V DC supply may be overloaded.
50 AMA calibra-
tion failed
X Contact the local Danfoss supplier.
51 15 AMA Unom,
Inom
X The setting of motor voltage, motor current, and motor
power is wrong. Check the settings.
52 AMA low In-
om
X The motor current is too low. Check the settings.
53 AMA big mo-
tor
X The motor is too big to perform AMA.
54 AMA small
mot
X The motor is too small to perform AMA.
55 AMA par.
range
X The parameter values found from the motor are outside
the acceptable range.
56 AMA user in-
terrupt
X The AMA has been interrupted by the user.
57 AMA timeout X Try to start the AMA again a number of times, until the
AMA is carried out.
NOTICE
Repeated runs may heat the motor to a level
where the resistance R
s
and R
r
are increased. In
most cases, however, this is not critical.
58 AMA internal X X Contact the local Danfoss supplier.
59 25 Current limit X The current is higher than the value in parameter 4-18
Current Limit.
60 44 External In-
terlock
X External interlock has been activated. To resume normal
operation, apply 24 V DC to the terminal programmed for
external interlock and reset the drive (via serial communi-
cation, digital I/O, or by pressing [Reset] key on the LCP).
66 26 Heat sink
Temperature
Low
X This warning is based on the temperature sensor in the
IGBT module (on 400 V, 30–90 kW (40–125 hp) and 600 V
units).
69 1 Pwr. Card
Temp
X X X The temperature sensor on the power card exceeds the
upper or lower limits.
70 36 Illegal FC
configuration
X X The control card and power card are not matched.
79 Illegal power
section con-
figuration
X X Internal fault. Contact the local Danfoss supplier.
Warnings and Alarms
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078