Parameter Option Default Usage
Parameter 4-19
Max Output
Frequency
0.0–400.0 Hz 100 Hz Enter the maximum output frequency value. If parameter 4-19
Max Output Frequency is set lower than parameter 4-14 Motor
Speed High Limit [Hz], parameter 4-14 Motor Speed High Limit
[Hz] is set equal to parameter 4-19 Max Output Frequency auto-
matically.
Parameter 5-40
Function Relay
See parameter 5-40 Function
Relay.
[9] Alarm Select the function to control output relay 1.
Parameter 5-40
Function Relay
See parameter 5-40 Function
Relay.
[5] Drive run-
ning
Select the function to control output relay 2.
Parameter 6-10
Terminal 53
Low Voltage
0.00–10.00 V 0.07 V Enter the voltage that corresponds to the low reference value.
Parameter 6-11
Terminal 53
High Voltage
0.00–10.00 V 10 V Enter the voltage that corresponds to the high reference val-
ue.
Parameter 6-12
Terminal 53
Low Current
0.00–20.00 mA 4 mA Enter the current that corresponds to the low reference value.
Parameter 6-13
Terminal 53
High Current
0.00–20.00 mA 20 mA Enter the current that corresponds to the high reference val-
ue.
Parameter 6-19
Terminal 53
mode
[0] Current
[1] Voltage
[1] Voltage Select if terminal 53 is used for current or voltage input.
Parameter
30-22 Locked
Rotor Detection
[0] Off
[1] On
[0] Off
Parameter
30-23 Locked
Rotor Detection
Time [s]
0.05–1 s 0.10 s
Programming
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 47