Manual
Table Of Contents
- VLT® HVAC Basic Drive FC 101
- English US
- Contents
- Introduction
- Safety
- Installation
- Mechanical Installation
- Electrical Installation
- Electrical Installation in General
- IT Mains
- Mains and Motor Connection
- Introduction
- Connecting to Mains and Motor
- Relays and Terminals on Enclosure Sizes H1–H5
- Relays and Terminals on Enclosure Size H6
- Relays and Terminals on Enclosure Size H7
- Relays and Terminals on Enclosure Size H8
- Connecting to Mains and Motor for Enclosure Size H9
- Relays and Terminals on Enclosure Size H10
- Enclosure Size I2
- Enclosure Size I3
- Enclosure Size I4
- IP54 Enclosure Sizes I2, I3, I4
- Enclosure size I6
- Enclosure size I7, I8
- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
Parameter Option Default Usage
Parameter 4-19
Max Output
Frequency
0.0–400.0 Hz 100 Hz Enter the maximum output frequency value. If parameter 4-19
Max Output Frequency is set lower than parameter 4-14 Motor
Speed High Limit [Hz], parameter 4-14 Motor Speed High Limit
[Hz] is set equal to parameter 4-19 Max Output Frequency auto-
matically.
Parameter 5-40
Function Relay
See parameter 5-40 Function
Relay.
[9] Alarm Select the function to control output relay 1.
Parameter 5-40
Function Relay
See parameter 5-40 Function
Relay.
[5] Drive run-
ning
Select the function to control output relay 2.
Parameter 6-10
Terminal 53
Low Voltage
0.00–10.00 V 0.07 V Enter the voltage that corresponds to the low reference value.
Parameter 6-11
Terminal 53
High Voltage
0.00–10.00 V 10 V Enter the voltage that corresponds to the high reference val-
ue.
Parameter 6-12
Terminal 53
Low Current
0.00–20.00 mA 4 mA Enter the current that corresponds to the low reference value.
Parameter 6-13
Terminal 53
High Current
0.00–20.00 mA 20 mA Enter the current that corresponds to the high reference val-
ue.
Parameter 6-19
Terminal 53
mode
[0] Current
[1] Voltage
[1] Voltage Select if terminal 53 is used for current or voltage input.
Parameter
30-22 Locked
Rotor Detection
[0] Off
[1] On
[0] Off –
Parameter
30-23 Locked
Rotor Detection
Time [s]
0.05–1 s 0.10 s –
Programming
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 47
Danfoss A/S © 2019.11