- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
3x380–480 V
IP54
0.75 (1) – PKZM0-16 FRS-R-10 KTS-R-10 JKS-10 JJS-10 16
1.5 (2) PKZM0-16 FRS-R-10 KTS-R-10 JKS-10 JJS-10 16
2.2 (3) PKZM0-16 FRS-R-15 KTS-R-15 JKS-15 JJS-15 16
3 (4) PKZM0-16 FRS-R-15 KTS-R-15 JKS-15 JJS-15 16
4 (5) PKZM0-16 FRS-R-15 KTS-R-15 JKS-15 JJS-15 16
5.5 (7.5) PKZM0-25 FRS-R-25 KTS-R-25 JKS-25 JJS-25 25
7.5 (10) PKZM0-25 FRS-R-25 KTS-R-25 JKS-25 JJS-25 25
11 (15) PKZM4-63 FRS-R-50 KTS-R-50 JKS-50 JJS-50 63
15 (20) PKZM4-63 FRS-R-50 KTS-R-50 JKS-50 JJS-50 63
18.5 (25) PKZM4-63 FRS-R-80 KTS-R-80 JKS-80 JJS-80 63
22 (30) Moeller NZMB1-
A125
– FRS-R-80 KTS-R-80 JKS-80 JJS-80 125
30 (40) FRS-R-125 KTS-R-125 JKS-125 JJS-125 125
37 (50) FRS-R-125 KTS-R-125 JKS-125 JJS-125 125
45 (60) Moeller NZMB2-
A160
– FRS-R-125 KTS-R-125 JKS-125 JJS-125 160
55 (70) FRS-R-200 KTS-R-200 JKS-200 JJS-200 160
75 (100) Moeller NZMB2-
A250
– FRS-R-200 KTS-R-200 JKS-200 JJS-200 200
90 (125) FRS-R-250 KTS-R-250 JKS-200 JJS-200 200
3.2.5 EMC-correct Electrical Installation
General points to be observed to ensure EMC-correct electrical installation:
• Use only shielded/armored motor cables and shielded/armored control cables.
• Ground the shield at both ends.
• Avoid installation with twisted shield ends (pigtails), because it reduces the shielding effect at high frequencies. Use the cable
clamps provided.
• Ensure the same potential between the drive and the ground potential of PLC.
• Use star washers and galvanically conductive installation plates.
Installation
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
34 | Danfoss A/S © 2019.11