3x380–480 V
IP54
0.75 (1) PKZM0-16 FRS-R-10 KTS-R-10 JKS-10 JJS-10 16
1.5 (2) PKZM0-16 FRS-R-10 KTS-R-10 JKS-10 JJS-10 16
2.2 (3) PKZM0-16 FRS-R-15 KTS-R-15 JKS-15 JJS-15 16
3 (4) PKZM0-16 FRS-R-15 KTS-R-15 JKS-15 JJS-15 16
4 (5) PKZM0-16 FRS-R-15 KTS-R-15 JKS-15 JJS-15 16
5.5 (7.5) PKZM0-25 FRS-R-25 KTS-R-25 JKS-25 JJS-25 25
7.5 (10) PKZM0-25 FRS-R-25 KTS-R-25 JKS-25 JJS-25 25
11 (15) PKZM4-63 FRS-R-50 KTS-R-50 JKS-50 JJS-50 63
15 (20) PKZM4-63 FRS-R-50 KTS-R-50 JKS-50 JJS-50 63
18.5 (25) PKZM4-63 FRS-R-80 KTS-R-80 JKS-80 JJS-80 63
22 (30) Moeller NZMB1-
A125
FRS-R-80 KTS-R-80 JKS-80 JJS-80 125
30 (40) FRS-R-125 KTS-R-125 JKS-125 JJS-125 125
37 (50) FRS-R-125 KTS-R-125 JKS-125 JJS-125 125
45 (60) Moeller NZMB2-
A160
FRS-R-125 KTS-R-125 JKS-125 JJS-125 160
55 (70) FRS-R-200 KTS-R-200 JKS-200 JJS-200 160
75 (100) Moeller NZMB2-
A250
FRS-R-200 KTS-R-200 JKS-200 JJS-200 200
90 (125) FRS-R-250 KTS-R-250 JKS-200 JJS-200 200
3.2.5 EMC-correct Electrical Installation
General points to be observed to ensure EMC-correct electrical installation:
Use only shielded/armored motor cables and shielded/armored control cables.
Ground the shield at both ends.
Avoid installation with twisted shield ends (pigtails), because it reduces the shielding effect at high frequencies. Use the cable
clamps provided.
Ensure the same potential between the drive and the ground potential of PLC.
Use star washers and galvanically conductive installation plates.