3.2.4.5 Recommendation of Fuses and Circuit Breakers
NOTICE
In the event of malfunction, failure to follow the protection recommendation may result in damage to the drive.
Table 12: Fuses and Circuit Breakers
Circuit breaker Fuse
UL Non-UL UL Non-UL
Bussmann Bussmann Bussmann Bussmann Maxi‐
mum
fuse
Power [kW
(hp)]
Type RK5 Type RK1 Type J Type T Type G
3x200–240 V
IP20
0.25 (0.33) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.37 (0.5) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.75 (1) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
1.5 (2) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
2.2 (3) FRS-R-15 KTN-R15 JKS-15 JJN-15 16
3.7 (5) FRS-R-25 KTN-R25 JKS-25 JJN-25 25
5.5 (7.5) FRS-R-50 KTN-R50 JKS-50 JJN-50 50
7.5 (10) FRS-R-50 KTN-R50 JKS-50 JJN-50 50
11 (15) FRS-R-80 KTN-R80 JKS-80 JJN-80 65
15 (20) Cutler-Hammer
EGE3100FFG
Moeller NZMB1-
A125
FRS-R-100 KTN-R100 JKS-100 JJN-100 125
18.5 (25) FRS-R-100 KTN-R100 JKS-100 JJN-100 125
22 (30) Cutler-Hammer
JGE3150FFG
Moeller NZMB1-
A160
FRS-R-150 KTN-R150 JKS-150 JJN-150 160
30 (40) FRS-R-150 KTN-R150 JKS-150 JJN-150 160
37 (50) Cutler-Hammer
JGE3200FFG
Moeller NZMB1-
A200
FRS-R-200 KTN-R200 JKS-200 JJN-200 200
45 (60) FRS-R-200 KTN-R200 JKS-200 JJN-200 200
3x380–480 V
IP20