Manual
Table Of Contents
- VLT® HVAC Basic Drive FC 101
- English US
- Contents
- Introduction
- Safety
- Installation
- Mechanical Installation
- Electrical Installation
- Electrical Installation in General
- IT Mains
- Mains and Motor Connection
- Introduction
- Connecting to Mains and Motor
- Relays and Terminals on Enclosure Sizes H1–H5
- Relays and Terminals on Enclosure Size H6
- Relays and Terminals on Enclosure Size H7
- Relays and Terminals on Enclosure Size H8
- Connecting to Mains and Motor for Enclosure Size H9
- Relays and Terminals on Enclosure Size H10
- Enclosure Size I2
- Enclosure Size I3
- Enclosure Size I4
- IP54 Enclosure Sizes I2, I3, I4
- Enclosure size I6
- Enclosure size I7, I8
- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
The dimensions are only for the physical units. When installing in an application, allow space above and below the units for cooling.
The amount of space for free air passage is listed in 3.1.1 Side-by-side Installation.
3.2 Electrical Installation
3.2.1 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors are
required. 75 °C (167 °F) is recommended.
Table 9: Tightening Torques for Enclosure Sizes H1–H8, 3x200–240 V & 3x380–480 V
Power [kW (hp)] Torque [Nm (in-lb)]
Enclo‐
sure
size
IP class 3x200–240 V 3x380–480 V Mains Motor DC con‐
nection
Control
terminals
Ground Relay
H1 IP20 0.25–1.5
(0.33–2)
0.37–1.5
(0.5–2)
0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
H2 IP20 2.2 (3) 2.2–4.0 (3–5) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
H3 IP20 3.7 (5) 5.5–7.5 (7.5–10) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
H4 IP20 5.5–7.5
(7.5–10)
11–15
(15–20)
1.2 (11) 1.2 (11) 1.2 (11) 0.5 (4) 0.8 (7) 0.5 (4)
H5 IP20 11 (15) 18.5–22 (25–30) 1.2 (11) 1.2 (11) 1.2 (11) 0.5 (4) 0.8 (7) 0.5 (4)
H6 IP20 15–18.5
(20–25)
30–45
(40–60)
4.5 (40) 4.5 (40) – 0.5 (4) 3 (27) 0.5 (4)
H7 IP20 22–30 (30–40) 55 (70) 10 (89) 10 (89) – 0.5 (4) 3 (27) 0.5 (4)
H7 IP20 – 75 (100) 14 (124) 14 (124) – 0.5 (4) 3 (27) 0.5 (4)
H8 IP20 37–45 (50–60) 90 (125)
24 (212)
(1)
24 (212)
(1)
– 0.5 (4) 3 (27) 0.5 (4)
1
Cable dimensions >95 mm
2
.
Table 10: Tightening Torques for Enclosure Sizes I2–I8
Power [kW (hp)] Torque [Nm (in-lb)]
Enclosure
size
IP class 3x380–480 V Mains Motor DC connec‐
tion
Control ter‐
minals
Ground Relay
I2 IP54 0.75–4.0 (1–5) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
I3 IP54 5.5–7.5 (7.5–10) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
I4 IP54 11–18.5 (15–25) 1.2 (11) 1.2 (11) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
I6 IP54 22–37 (30–50) 4.5 (40) 4.5 (40) – 0.5 (4) 3 (27) 0.6 (5)
I7 IP54 45–55 (60–70) 10 (89) 10 (89) – 0.5 (4) 3 (27) 0.6 (5)
Installation
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 15