FC101 Design Guide

Modbus telegram. Coil 127 decimal is addressed as coil
007Ehex (126 decimal).
Holding register 40001 is addressed as register 0000 in the
data address eld of the telegram. The function code eld
already species a holding register operation. Therefore,
the 4XXXX reference is implicit. Holding register 40108 is
addressed as register 006Bhex (107 decimal).
Coil
number
Description
Signal
direction
1–16
Frequency converter control word
(see Table 7.16).
Master to slave
17–32
Frequency converter speed or
setpoint reference range 0x0–
0xFFFF (-200% ... ~200%).
Master to slave
33–48
Frequency converter status word
(see Table 7.17).
Slave to master
49–64
Open-loop mode: Frequency
converter output frequency.
Closed-loop mode: Frequency
converter feedback signal.
Slave to master
65
Parameter write control (master to
slave).
Master to slave
0 = Parameter changes are written
to the RAM of the frequency
converter.
1 = Parameter changes are written
to the RAM and EEPROM of the
frequency converter.
66–65536 Reserved.
Table 7.15 Coil Register
Coil 0 1
01 Preset reference lsb
02 Preset reference msb
03 DC brake No DC brake
04 Coast stop No coast stop
05 Quick stop No quick stop
06 Freeze frequency No freeze frequency
07 Ramp stop Start
08 No reset Reset
09 No jog Jog
10 Ramp 1 Ramp 2
11 Data not valid Data valid
12 Relay 1 o Relay 1 on
13 Relay 2 o Relay 2 on
14 Set up lsb
15
16 No reversing Reversing
Table 7.16 Frequency Converter Control Word (FC Prole)
Coil 0 1
33 Control not ready Control ready
34
Frequency converter not
ready
Frequency converter ready
35 Coast stop Safety closed
36 No alarm Alarm
37 Not used Not used
38 Not used Not used
39 Not used Not used
40 No warning Warning
41 Not at reference At reference
42 Hand mode Auto mode
43 Out of frequency range In frequency range
44 Stopped Running
45 Not used Not used
46 No voltage warning Voltage exceeds
47 Not in current limit Current limit
48 Thermal level is OK Thermal level exceeds
Table 7.17 Frequency Converter Status Word (FC Prole)
RS485 Installation and Set-... Design Guide
MG18C822 Danfoss A/S © 04/2018 All rights reserved. 93
7 7