FC101 Design Guide

6.4 Quick Transfer of Parameter Settings
between Multiple Frequency Converters
When the set-up of a frequency converter is completed,
store the data in the LCP or on a PC via MCT 10 Set-up
Software.
Data transfer from the frequency converter to the LCP
1. Go to parameter 0-50 LCP Copy.
2. Press [OK].
3. Select [1] All to LCP.
4. Press [OK].
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
Data transfer from the LCP to the frequency converter
1. Go to parameter 0-50 LCP Copy.
2. Press [OK].
3. Select [2] All from LCP.
4. Press [OK].
6.5 Readout and Programming of Indexed
Parameters
Select the parameter, press [OK], and press [
]/[
] to scroll
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by pressing [
]/[
]. Press [OK] to accept the new
setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.
6.6
Initialization to Default Settings
There are 2 ways to initialize the frequency converter to
the default settings.
Recommended initialization
1. Select parameter 14-22 Operation Mode.
2. Press [OK].
3. Select [2] Initialisation and Press [OK].
4. Power o the frequency converter and wait until
the display turns o.
5. Reconnect the mains supply. The frequency
converter is now reset, except for the following
parameters:
Parameter 1-06 Clockwise Direction
Parameter 8-30 Protocol
Parameter 8-31 Address
Parameter 8-32 Baud Rate
Parameter 8-33 Parity / Stop Bits
Parameter 8-35 Minimum Response Delay
Parameter 8-36 Maximum Response Delay
Parameter 8-37 Maximum Inter-char delay
Parameter 8-70 BACnet Device Instance
Parameter 8-72 MS/TP Max Masters
Parameter 8-73 MS/TP Max Info Frames
Parameter 8-74 "I am" Service
Parameter 8-75 Intialisation Password
Parameter 15-00 Operating hours to
parameter 15-05 Over Volt's
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter 15-30 Alarm Log: Error Code
Parameter group 15-4* Drive identication
Parameter 18-10 FireMode Log:Event
2-nger initialization
The other way to initialize the frequency converter to
default settings is through 2-nger initialization:
1. Power o the frequency converter.
2. Press [OK] and [Menu].
3. Power up the frequency converter while still
pressing the keys for 10 s.
4. The frequency converter is now reset, except for
the following parameters:
Parameter 1-06 Clockwise Direction
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter group 15-4* Drive identication
Parameter 18-10 FireMode Log:Event
Initialization of parameters is conrmed by alarm 80, Drive
initialised in the display after the power cycle.