FC101 Design Guide

Parameter Range Default Usage
Parameter 20-94 PI Integral
Time
0.1–999.0 s 999.0 s Enter the process controller integral time. Obtain quick
control through a short integral time, though if the
integral time is too short, the process becomes unstable.
An excessively long integral time disables the integral
action.
Parameter 30-22 Locked Rotor
Protection
[0] O
[1] On
[0] O
Parameter 30-23 Locked Rotor
Detection Time [s]
0.05–1.00 s 0.10 s
Table 6.5 Set-up Wizard for Closed-loop Applications
Motor set-up
The motor set-up wizard guides users through the needed motor parameters.
Parameter Range Default Usage
Parameter 0-03 Regional
Settings
[0] International
[1] US
0
Parameter 0-06 GridType [0]–[132] see Table 6.4. Size related Select the operating mode for restart after reconnection of
the frequency converter to mains voltage after power-
down.