FC101 Design Guide

6 Programming
6.1 Introduction
The frequency converter can be programmed from the LCP
or from a PC via the RS485 COM port by installing the MCT
10 Set-up Software. Refer to chapter 1.5 Additional
Resources for more details about the software.
6.2 Local Control Panel (LCP)
The LCP is divided into 4 functional sections.
A. Display
B. Menu key
C. Navigation keys and indicator lights
D. Operation keys and indicator lights
130BB765.11
B
a
c
k
Com.
1-20 Motor Power
[5] 0.37kW - 0.5HP
Setup 1
A
B
1
12
13
14
15
11
11
10
9
8
7
6
5
4
3
2
C
D
S
t
a
tus
M
ain
M
enu
Q
uick
M
enu
Hand
On
OK
M
enu
Off
Reset
Auto
On
Alarm
Warn.
On
11
Figure 6.1 Local Control Panel (LCP)
A. Display
The LCD display is illuminated with 2 alphanumeric lines.
All data is shown on the LCP.
Figure 6.1 describes the information that can be read from
the display.
1 Parameter number and name.
2 Parameter value.
3
Set-up number shows the active set-up and the edit set-up.
If the same set-up acts as both active and edit set-up, only
that set-up number is shown (factory setting). When active
and edit set-up dier, both numbers are shown in the
display (set-up 12). The number ashing indicates the edit
set-up.
4
Motor direction is shown to the bottom left of the display
indicated by a small arrow pointing either clockwise or
counterclockwise.
5
The triangle indicates if the LCP is in Status, Quick Menu, or
Main Menu.
Table 6.1 Legend to Figure 6.1, Part I
B. Menu key
Press [Menu] to select among Status, Quick Menu, or Main
Menu.
C. Navigation keys and indicator lights
6 Com. LED: Flashes during bus communication.
7 Green LED/On: Control section is working correctly.
8 Yellow LED/Warn.: Indicates a warning.
9 Flashing Red LED/Alarm: Indicates an alarm.
10
[Back]: For moving to the previous step or layer in the
navigation structure.
11
[
] [
] []: For navigating among parameter groups and
parameters, and within parameters. They can also be used
for setting local reference.
12
[OK]: For selecting a parameter and for accepting changes
to parameter settings.
Table 6.2 Legend to Figure 6.1, Part II
D. Operation keys and indicator lights
13
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTICE!
[2] Coast inverse is the default option for
parameter 5-12 Terminal 27 Digital Input. If there is
no 24 V supply to terminal 27, [Hand On] does not
start the motor. Connect terminal 12 to terminal 27.
14
[O/Reset]: Stops the motor (O). If in alarm mode, the
alarm is reset.
15
[Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
Table 6.3 Legend to Figure 6.1, Part III
Programming Design Guide
MG18C822 Danfoss A/S © 04/2018 All rights reserved. 67
6
6