FC101 Design Guide
5.1.1 Mains and Motor Connection
The frequency converter is designed to operate all
standard 3-phase asynchronous motors. For maximum
cross-section on cables, see chapter 8.4 General Technical
Data.
•
Use a shielded/armored motor cable to comply
with EMC emission
specications and connect
this cable to both the decoupling plate and the
motor.
•
Keep the motor cable as short as possible to
reduce the noise level and leakage currents.
•
For further details on mounting the decoupling
plate, see FC 101 Decoupling Plate Mounting
Instruction.
•
Also see EMC-Correct Installation in
chapter 5.1.2 EMC-compliant Electrical Installation.
•
For details on how to connect the frequency
converter to mains and motor, see chapter
Connecting to Mains and Motor in the VLT
®
HVAC
Basic Drive FC 101 Quick Guide.
Relays and terminals on enclosure sizes H1–H5
130BB634.10
1
2
2
3
4
Motor
U
V
W
-DC
+DC
MAINS
1 Mains
2 Ground
3 Motor
4 Relays
Figure 5.2 Enclosure Sizes H1–H5
IP20, 200–240 V, 0.25–11 kW (0.33–15 hp)
IP20, 380–480 V, 0.37–22 kW (0.5–30 hp)
Installation
VLT
®
HVAC Basic Drive FC 101
58 Danfoss A/S © 04/2018 All rights reserved. MG18C822
55