FC101 Design Guide
4.3.2 Harmonic Filters
3x380–480 V 50 Hz
Power
[kW
(hp)]
Frequency
converter
input
current
continuous
[A]
Default
switching
frequency
[kHz]
THDi
level
[%]
Order
number
lter IP00
Code
number
lter IP20
22
(30)
41.5 4 4 130B1397 130B1239
30
(40)
57 4 3 130B1398 130B1240
37
(50)
70 4 3 130B1442 130B1247
45
(60)
84 3 3 130B1442 130B1247
55
(74)
103 3 5 130B1444 130B1249
75
(100)
140 3 4 130B1445 130B1250
90
(120)
176 3 4 130B1445 130B1250
Table 4.7 AHF Filters (5% Current Distortion)
3x380–480 V 50 Hz
Power
[kW
(hp)]
Frequency
converter
input
current
continuous
[A]
Default
switching
frequency
[kHz]
THDi
level
[%]
Order
number
lter IP00
Code
number
lter IP20
22
(30)
41.5 4 6 130B1274 130B1111
30
(40)
57 4 6 130B1275 130B1176
37
(50)
70 4 9 130B1291 130B1201
45
(60)
84 3 9 130B1291 130B1201
55
(74)
103 3 9 130B1292 130B1204
75
(100)
140 3 8 130B1294 130B1213
90
(120)
176 3 8 130B1294 130B1213
Table 4.8 AHF Filters (10% Current Distortion)
3x440–480 V 60 Hz
Power
[kW
(hp)]
Frequency
converter
input
current
Continuous
[A]
Default
switching
frequency
[kHz]
THDi
level
[%]
Order
number
lter IP00
Code
number
lter IP20
22
(30)
34.6 4 3 130B1792 130B1757
30
(40)
49 4 3 130B1793 130B1758
37
(50)
61 4 3 130B1794 130B1759
45
(60)
73 3 4 130B1795 130B1760
55
(74)
89 3 4 130B1796 130B1761
75
(100)
121 3 5 130B1797 130B1762
90
(120)
143 3 5 130B1798 130B1763
Table 4.9 AHF Filters (5% Current Distortion)
3x440–480 V 60 Hz
Power
[kW
(hp)]
Frequency
converter
input
current
continuous
[A]
Default
switching
frequency
[kHz]
THDi
level
[%]
Order
number
lter IP00
Code
number
lter IP20
22
(30)
34.6 4 6 130B1775 130B1487
30
(40)
49 4 8 130B1776 130B1488
37
(50)
61 4 7 130B1777 130B1491
45
(60)
73 3 9 130B1778 130B1492
55
(74)
89 3 8 130B1779 130B1493
75
(100)
121 3 9 130B1780 130B1494
90
(120)
143 3 10 130B1781 130B1495
Table 4.10 AHF Filters (10% Current Distortion)
Selection and Ordering
VLT
®
HVAC Basic Drive FC 101
54 Danfoss A/S © 04/2018 All rights reserved. MG18C822
44