FC101 Design Guide
3.4.3 EMC Emission Test Results
The following test results have been obtained using a system with a frequency converter, a shielded control cable, a control
box with potentiometer, and a shielded motor cable.
RFI lter
type
Conduct emission. Maximum shielded cable length [m (ft)] Radiated emission
Industrial environment
EN 55011
Class A Group 2
Industrial environment
Class A Group 1
Industrial environment
Class B
Housing, trades and
light industries
Class A Group 1
Industrial environment
Class B
Housing, trades and
light industries
EN/IEC
61800-3
Category C3
Second environment
Industrial
Category C2
First environment
Home and oce
Category C1
First environment
Home and oce
Category C2
First environment
Home and oce
Category C1
First environment
Home and oce
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
H4 RFI lter (EN55011 A1, EN/IEC61800-3 C2)
0.25–11 kW
(0.34–15 hp)
3x200–240 V
IP20
– – 25 (82) 50 (164) – 20 (66) Yes Yes – No
0.37–22 kW
(0.5–30 hp)
3x380–480 V
IP20
– – 25 (82) 50 (164) – 20 (66) Yes Yes – No
H2 RFI lter (EN 55011 A2, EN/IEC 61800-3 C3)
15–45 kW
(20–60 hp)
3x200–240 V
IP20
25 (82) – – – – – No – No –
30–90 kW
(40–120 hp)
3x380–480 V
IP20
25 (82) – – – – – No – No –
0.75–18.5 kW
(1–25 hp)
3x380–480 V
IP54
25 (82) – – – – – Yes – – –
22–90 kW
(30–120 hp)
3x380–480 V
IP54
25 (82) – – – – – No – No –
H3 RFI lter (EN55011 A1/B, EN/IEC 61800-3 C2/C1)
15–45 kW
(20–60 hp)
3x200–240 V
IP20
– – 50 (164) – 20 (66) – Yes – No –
30–90 kW
(40–120 hp)
3x380–480 V
IP20
– – 50 (164) – 20 (66) – Yes – No –
Product Overview
VLT
®
HVAC Basic Drive FC 101
40 Danfoss A/S © 04/2018 All rights reserved. MG18C822
33