FC101 Design Guide

8.5 dU/Dt
Cable length [m (ft)] AC line voltage [V]
Rise time [μsec]
V
peak
[kV]
dU/dt [kV/μsec]
200 V 0.25 kW (0.34 hp)
5 (16) 240 0.121 0.498 3.256
25 (82) 240 0.182 0.615 2.706
50 (164) 240 0.258 0.540 1.666
200 V 0.37 kW (0.5 hp)
5 (16) 240 0.121 0.498 3.256
25 (82) 240 0.182 0.615 2.706
50 (164) 240 0.258 0.540 1.666
200 V 0.75 kW (1.0 hp)
5 (16) 240 0.121 0.498 3.256
25 (82) 240 0.182 0.615 2.706
50 (164) 240 0.258 0.540 1.666
200 V 1.5 kW (2.0 hp)
5 (16) 240 0.121 0.498 3.256
25 (82) 240 0.182 0.615 2.706
50 (164) 240 0.258 0.540 1.666
200 V 2.2 kW (3.0 hp)
5 (16) 240 0.18 0.476 2.115
25 (82) 240 0.230 0.615 2.141
50 (164) 240 0.292 0.566 1.550
200 V 3.7 kW (5.0 hp)
5 (16) 240 0.168 0.570 2.714
25 (82) 240 0.205 0.615 2.402
50 (164) 240 0.252 0.620 1.968
200 V 5.5 kW (7.4 hp)
5 (16) 240 0.128 0.445 2.781
25 (82) 240 0.224 0.594 2.121
50 (164) 240 0.328 0.596 1.454
200 V 7.5 kW (10 hp)
5 (16) 240 0.18 0.502 2.244
25 (82) 240 0.22 0.598 2.175
50 (164) 240 0.292 0.615 1.678
200 V 11 kW (15 hp)
36 (118) 240 0.176 0.56 2.545
50 (164) 240 0.216 0.599 2.204
400 V 0.37 kW (0.5 hp)
5 (16) 400 0.160 0.808 4.050
25 (82) 400 0.240 1.026 3.420
50 (164) 400 0.340 1.056 2.517
400 V 0.75 kW (1.0 hp)
5 (16) 400 0.160 0.808 4.050
25 (82) 400 0.240 1.026 3.420
50 (164) 400 0.340 1.056 2.517
400 V 1.5 kW (2.0 hp)
5 (16) 400 0.160 0.808 4.050
25 (82) 400 0.240 1.026 3.420
50 (164) 400 0.340 1.056 2.517
400 V 2.2 kW (3.0 hp)
5 (16) 400 0.190 0.760 3.200
25 (82) 400 0.293 1.026 2.801
50 (164) 400 0.422 1.040 1.971
400 V 3.0 kW (4.0 hp)
5 (16) 400 0.190 0.760 3.200
25 (82) 400 0.293 1.026 2.801
50 (164) 400 0.422 1.040 1.971
400 V 4.0 kW (5.4 hp)
5 (16) 400 0.190 0.760 3.200
25 (82) 400 0.293 1.026 2.801
50 (164) 400 0.422 1.040 1.971
400 V 5.5 kW (7.4 hp)
5 (16) 400 0.168 0.81 3.857
25 (82) 400 0.239 1.026 3.434
50 (164) 400 0.328 1.05 2.560
General Specications Design Guide
MG18C822 Danfoss A/S © 04/2018 All rights reserved. 123