8.3 Fuses and Circuit Breakers
Branch circuit protection
To prevent re hazards, protect the branch circuits in an
installation - switch gear, machines, and so on - against
short circuits and overcurrent. Follow national and local
regulations.
Short-circuit protection
Danfoss recommends using the fuses and circuit breakers
listed in Table 8.11 to protect service personnel or other
equipment in case of an internal failure in the unit or a
short circuit on the DC link. The frequency converter
provides full short-circuit protection in case of a short
circuit on the motor.
Overcurrent protection
Provide overload protection to avoid overheating of the
cables in the installation. Overcurrent protection must
always be carried out according to local and national
regulations. Circuit breakers and fuses must be designed
for protection in a circuit capable of supplying a maximum
of 100000 A
rms
(symmetrical), 480 V maximum.
UL/Non-UL compliance
To ensure compliance with UL or IEC 61800-5-1, use the
circuit breakers or fuses listed in Table 8.11.
Circuit breakers must be designed for protection in a
circuit capable of supplying a maximum of 10000 A
rms
(symmetrical), 480 V maximum.
NOTICE!
In the event of malfunction, failure to follow the
protection recommendation may result in damage to the
frequency converter.
Circuit breaker Fuse
UL Non-UL UL Non-UL
Bussmann Bussmann Bussmann Bussmann
Maximum
fuse
Power [kW (hp)] Type RK5 Type RK1 Type J Type T Type G
3x200–240 V IP20
0.25 (0.33)
– –
FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.37 (0.5) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.75 (1.0) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
1.5 (2.0) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
2.2 (3.0) FRS-R-15 KTN-R15 JKS-15 JJN-15 16
3.7 (5.0) FRS-R-25 KTN-R25 JKS-25 JJN-25 25
5.5 (7.5) FRS-R-50 KTN-R50 JKS-50 JJN-50 50
7.5 (10) FRS-R-50 KTN-R50 JKS-50 JJN-50 50
11 (15) FRS-R-80 KTN-R80 JKS-80 JJN-80 65
15 (20)
Cutler-Hammer
EGE3100FFG
Moeller NZMB1-
A125
FRS-R-100 KTN-R100 JKS-100 JJN-100 125
18.5 (25) FRS-R-100 KTN-R100 JKS-100 JJN-100 125
22 (30)
Cutler-Hammer
JGE3150FFG
Moeller NZMB1-
A160
FRS-R-150 KTN-R150 JKS-150 JJN-150 160
30 (40) FRS-R-150 KTN-R150 JKS-150 JJN-150 160
37 (50)
Cutler-Hammer
JGE3200FFG
Moeller NZMB1-
A200
FRS-R-200 KTN-R200 JKS-200 JJN-200 200
45 (60) FRS-R-200 KTN-R200 JKS-200 JJN-200 200