FC101 Design Guide
8.2 Mains Supply Specications
8.2.1 3x200–240 V AC
Frequency converter PK25 PK37 PK75 P1K5 P2K2 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
Typical shaft output [kW] 0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0
Typical shaft output [hp] 0.33 0.5 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0
Enclosure protection rating
IP20
H1 H1 H1 H1 H2 H3 H4 H4 H5 H6 H6 H7 H7 H8 H8
Maximum cable size in
terminals (mains, motor)
[mm
2
(AWG)]
4
(10)
4
(10)
4
(10)
4
(10)
4
(10)
4
(10)
16
(6)
16
(6)
16
(6)
35
(2)
35
(2)
50
(1)
50
(1)
95
(0)
120
(4/0)
Output current
40 °C (104 °F) ambient temperature
Continuous
(3x200–240 V) [A]
1.5 2.2 4.2 6.8 9.6 15.2 22.0 28.0 42.0 59.4 74.8 88.0 115.0 143.0 170.0
Intermittent
(3x200–240 V) [A]
1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8 46.2 65.3 82.3 96.8 126.5 157.3 187.0
Maximum input current
Continuous
(3x200–240 V) [A]
1.1 1.6 2.8 5.6
8.6/
7.2
14.1/
12.0
21.0/
18.0
28.3/
24.0
41.0/
38.2
52.7 65.0 76.0 103.7 127.9 153.0
Intermittent
(3x200–240 V) [A]
1.2 1.8 3.1 6.2
9.5/
7.9
15.5/
13.2
23.1/
19.8
31.1/
26.4
45.1/
42.0
58.0 71.5 83.7 114.1 140.7 168.3
Maximum mains fuses See chapter 8.3.1 Fuses and Circuit Breakers.
Estimated power loss [W],
Best case/typical
1)
12/
14
15/
18
21/
26
48/
60
80/
102
97/
120
182/
204
229/
268
369/
386
512 697 879 1149 1390 1500
Weight enclosure
protection rating IP20 [kg
(lb)]
2.0
(4.4)
2.0
(4.4)
2.0
(4.4)
2.1
(4.6)
3.4
(7.5)
4.5
(9.9)
7.9
(17.4)
7.9
(17.4)
9.5
(20.9)
24.5
(54)
24.5
(54)
36.0
(79.4)
36.0
(79.4)
51.0
(112.4
)
51.0
(112.4
)
Eciency [%], best case/
typical
2)
97.0/
96.5
97.3/
96.8
98.0/
97.6
97.6/
97.0
97.1/
96.3
97.9/
97.4
97.3/
97.0
98.5/
97.1
97.2/
97.1
97.0 97.1 96.8 97.1 97.1 97.3
Output current
50 °C (122 °F) ambient temperature
Continuous
(3x200–240 V) [A]
1.5 1.9 3.5 6.8 9.6 13.0 19.8 23.0 33.0 41.6 52.4 61.6 80.5 100.1 119
Intermittent
(3x200–240 V) [A]
1.7 2.1 3.9 7.5 10.6 14.3 21.8 25.3 36.3 45.8 57.6 67.8 88.6 110.1 130.9
Table 8.5 3x200–240 V AC, 0.25–45 kW (0.33–60 hp)
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to
drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
2) Eciency measured at nominal current. For energy eciency class, see chapter 8.4.12 Ambient Conditions. For part load losses, see
drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
General Specications
VLT
®
HVAC Basic Drive FC 101
110 Danfoss A/S © 04/2018 All rights reserved. MG18C822
88