FC101 Design Guide

A
a
b
B
C
D
130BB614.10
e
f
a
d
e
130BC205.10
e
f
a
e
130BC246.10
Enclosure Power [kW (hp)] Height [mm (in)] Width [mm (in)]
Depth
[mm (in)]
Mounting hole [mm (in)]
Maximum
weight
Size IP class 3x200–240 V 3x380–480 V 3x525–600 V A
A
1)
a B b C d e f kg (lb)
I2 IP54
0.75–4.0
(1.0–5.0)
332
(13.1)
318.5
(12.53)
115 (4.5) 74 (2.9) 225 (8.9) 11 (0.43)
5.5
(0.22)
9 (0.35) 5.3 (11.7)
I3 IP54 5.5–7.5 (7.5–10)
368
(14.5)
354 (13.9) 135 (5.3) 89 (3.5) 237 (9.3) 12 (0.47)
6.5
(0.26)
9.5 (0.37) 7.2 (15.9)
I4 IP54
11–18.5 (15–
25)
476
(18.7)
460 (18.1) 180 (7.0) 133 (5.2) 290 (11.4) 12 (0.47)
6.5
(0.26)
9.5 (0.37)
13.8
(30.42)
I6 IP54 22–37 (30–50)
650
(25.6)
624 (24.6) 242 (9.5) 210 (8.3) 260 (10.2) 19 (0.75) 9 (0.35) 9 (0.35) 27 (59.5)
I7 IP54 45–55 (60–70)
680
(26.8)
648 (25.5) 308 (12.1) 272 (10.7) 310 (12.2) 19 (0.75) 9 (0.35) 9.8 (0.39) 45 (99.2)
I8 IP54
75–90 (100–
125)
770 (30) 739 (29.1) 370 (14.6) 334 (13.2) 335 (13.2) 19 (0.75) 9 (0.35) 9.8 (0.39) 65 (143.3)
1) Including decoupling plate
The dimensions are only for the physical units.
NOTICE!
When installing in an application, allow space above and below the units for cooling. The amount of space for free air passage is listed in Table 8.1.
Table 8.3 Dimensions, Enclosure Sizes I2–I8
General Specications Design Guide
MG18C822 Danfoss A/S © 04/2018 All rights reserved. 107