FC101 Design Guide

7.11.2 Status Word According to FC Prole
(STW)
Set parameter 8-30 Protocol to [0] FC.
Output frequencySTW
Bit
Slave-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.12
Figure 7.16 Status Word
Bit Bit = 0 Bit = 1
00 Control not ready Control ready
01
Frequency converter not
ready
Frequency converter ready
02 Coasting Enable
03 No error Trip
04 No error Error (no trip)
05 Reserved
06 No error Triplock
07 No warning Warning
08
Speed reference
Speed = reference
09 Local operation Bus control
10 Out of frequency limit Frequency limit OK
11 No operation In operation
12 Frequency converter OK Stopped, auto start
13 Voltage OK Voltage exceeded
14 Current OK Current exceeded
15 Thermal level OK Thermal level exceeded
Table 7.39 Status Word According to FC Prole
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00 = 0: The frequency converter trips.
Bit 00 = 1: The frequency converter controls are ready but
the power component does not necessarily receive any
supply (if there is 24 V external supply to controls).
Bit 01, Frequency converter ready
Bit 01 = 0: The frequency converter is not ready.
Bit 01 = 1: The frequency converter is ready for operation,
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coast stop
Bit 02 = 0: The frequency converter releases the motor.
Bit 02 = 1: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03 = 0: The frequency converter is not in fault mode.
Bit 03 = 1: The frequency converter trips. To re-establish
operation, press [Reset].
Bit 04, No error/error (no trip)
Bit 04 = 0: The frequency converter is not in fault mode.
Bit 04 = 1: The frequency converter shows an error but
does not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06 = 0: The frequency converter is not in fault mode.
Bit 06 = 1: The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07 = 0: There are no warnings.
Bit 07 = 1: A warning has occurred.
Bit 08, Speed reference/speed = reference
Bit 08 = 0: The motor runs, but the present speed is
dierent from the preset speed reference. It might happen
when the speed ramps up/down during start/stop.
Bit 08 = 1: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09 = 0: [O/Reset] is activated on the control unit or [2]
Local in parameter 3-13 Reference Site is selected. It is not
possible to control the frequency converter via serial
communication.
Bit 09 = 1: It is possible to control the frequency converter
via the eldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10 = 0: The output frequency has reached the value in
parameter 4-12 Motor Speed Low Limit [Hz] or
parameter 4-14 Motor Speed High Limit [Hz].
Bit 10 = 1: The output frequency is within the dened
limits.
Bit 11, No operation/in operation
Bit 11 = 0: The motor is not running.
Bit 11 = 1: The frequency converter has a start signal
without coast.
Bit 12, Frequency converter OK/stopped, auto start
Bit 12 = 0: There is no temporary overtemperature on the
frequency converter.
Bit 12 = 1: The frequency converter stops because of
overtemperature but the unit does not trip and resumes
operation once the overtemperature normalizes.
Bit 13, Voltage OK/limit exceeded
Bit 13 = 0: There are no voltage warnings.
Bit 13 = 1: The DC voltage in the frequency converters DC
link is too low or too high.
RS485 Installation and Set-...
VLT
®
HVAC Basic Drive FC 101