FC101 Design Guide
Motor
f
JOG
The motor frequency when the jog function is activated
(via digital terminals).
f
M
The motor frequency.
f
MAX
The maximum motor frequency.
f
MIN
The minimum motor frequency.
f
M,N
The rated motor frequency (nameplate data).
I
M
The motor current.
I
M,N
The rated motor current (nameplate data).
n
M,N
The nominal motor speed (nameplate data).
P
M,N
The rated motor power (nameplate data).
U
M
The instantaneous motor voltage.
U
M,N
The rated motor voltage (nameplate data).
Break-away torque
175ZA078.10
Pull-out
RPM
Torque
Figure 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the
ratio between the power output and the power input.
Start-disable command
A stop command belonging to the group 1 control
commands, see Table 1.4.
Stop command
See Table 1.4.
Analog reference
A signal transmitted to the analog inputs 53 or 54. It can
be voltage or current.
•
Current input: 0–20 mA and 4–20 mA
•
Voltage input: 0–10 V DC
Bus reference
A signal transmitted to the serial communication port (FC
port).
Preset reference
A dened preset reference to be set from -100% to +100%
of the reference range. Selection of 8 preset references via
the digital terminals.
Ref
MAX
Determines the relationship between the reference input at
100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value set in
parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at
0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value is set in
parameter 3-02 Minimum Reference.
Analog inputs
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
•
Current input: 0–20 mA and 4–20 mA
•
Voltage input: 0–10 V DC
Analog outputs
The analog outputs can supply a signal of 0–20 mA, 4–
20 mA, or a digital signal.
Automatic motor adaptation, AMA
The AMA algorithm determines the electrical parameters
for the connected motor at standstill and compensates for
the resistance based on the length of the motor cable.
Digital inputs
The digital inputs can be used for controlling various
functions of the frequency converter.
Digital outputs
The frequency converter provides 2 solid-state outputs that
can supply a 24 V DC (maximum 40 mA) signal.
Relay outputs
The frequency converter provides 2 programmable relay
outputs.
Introduction
VLT
®
HVAC Basic Drive FC 101
8 Danfoss A/S © 04/2018 All rights reserved. MG18C822
11