Installation , Operation and Maintenance Instructions Genius
Service settings Supply air temperature
Cooling Mode setp.
Heating Mode setp.
Control parameters
Control parameters Room controller
P-band: 3°C
I-time: 20sec.
Supply control:
P-band: 70°C
I-time: 30sec.
Start hysteresis:
Heat pump starts
with a request > 30%
Start hysteresis: 0.3°C
Stop hysteresis: 0.3°C
Start delay: 60sec.
Stop delay:120sec
Service settings Speed Supply air fan SAF intense: 70%
SAF normal: 50%
SAF reduced: 35%
SAF humidity protect.: 15%
SAF night cool: 85%
Extract air fan
ETA intense: 70%
ETA normal: 50%
ETA reduced: 35%
ETA humidity protect.: 15%
ETA night cool: 85%
Power limitation
Activate: No
HP max: 100%
max. speed SEC 100%
min. speed SEC 60%
max. speed SEC
Setback operation:
100%
96
Control via Display
Genius - V 1.0