Installation , Operation and Maintenance Instructions Genius
Service settings Supply air temperature
Heat pump Hot Water Hot Water mode:
Automatic
Night cooling Night cooling active: No
Filter change Outdoor temp. night
Max.: 15.0 °C
min.: 5.0 °C
Room temp. min.: 20 °C
Active when outdoor temp.
22°C
Filter change
Reset alarm time Filter alarm
Reset alarm: No
Set alarm time Filter life
activation: 12 mon.
Time since last
change: 0 mon.
Service settings
Access Rights Heat pump Heat pump:
Modbus address = 1
Room designations Cong. Room 1 Room 1
Setpoint temp.: 20.0 °C
Deviation+: 3 °C
Deviation-: 3 °C
Room designation
Room 1
Denition Room 2 to 10
as Room 1
Language Choose language
English
93
Genius - V 1.0
Control via Display