10.8.1.6 Activate Supply Air Rooms/Room Controller
Heat pump
ModBus address 1
Activate supply air rooms
Number of rooms 6
Room 1
Modbus room address (ELA) 197
Room 2
Modbus room address (ELA) 39
Room 3
Modbus room address (ELA) 147
Room 4
Modbus room address (ELA) 82
Room 5
Modbus room address (ELA) 237
Room 6
Modbus room address (ELA) 200
Activate supply air rooms / room controller The control of the building service centre Genius is designed for a maximum
of 10 rooms. Since heating/cooling takes place in the supply air rooms, in
general, controllers are only installed in these rooms. Exception: if extract air
rooms are heated, e.g. via electrical underoor heating, these can also be
regulated by the room controller. These are installed in the appropriate rooms
(see page 67 "Individual room temperature control").
Number of rooms
ModBus address HP The ModBus address of the heat pump is xed with 1 and is not adjustable.
Room controller Each room controller of the type RC-CDO has its own address combination.
It must be entered in order to ensure communication with each other. The
addresses are located on the back of each controller (see „7 Commissioning“
page 25).
77
Genius - V 1.0
Operation/Control via Internet/App