Installation , Operation and Maintenance Instructions Genius
Speed
Speed
Supply air fan
Speed at intense ventilation 70 °C
Speed at nominal ventilation 50 °C
Speed at reduced ventilation 35 °C
Speed at hum. protect. ventilation. 15 °C
Speed at night cooling 85 °C
Extract air fan
Speed at intense ventilation 70 °C
Speed at nominal ventilation 50 °C
Speed at reduced ventilation 35 °C
Speed at hum. protect. ventilation. 15 °C
Speed at night cooling 85 °C
Secondary air fan
Parallel offset speed 100 %
Min. speed 60 %
max. speed 90 %
Power limitation
Activate No
WP max. 100 %
(see „7 Commissioning“ and „10.8.1.3 Night cooling“)
The speed values are generally set once during commissioning within this menu.
Secondary air fan Delivery setting Adjustment
range
Parallel offset speed 100 % 70 ... 100 % limits the max. speed of the secondary
air fan
Min. speed 60 % 50 ... 70 %
max. speed 90 % 60 ... 100 % max. speed durign night setback
Power limitation
Activate No If this is set to Yes, the power of the heat pump and sec-
ondary air fan will be limited
WP max. 100 % 50 ... 100 %
NOTE
The power of the system may only be limited in exceptional cases (e.g. very low heating/cooling load)
" Please discuss this limitation with the service company (see „7 Commissioning“ page 25).
72
Operation/Control via Internet/App
Genius - V 1.0