Installation , Operation and Maintenance Instructions Genius

Setting Manually
Factory settings 40°C
Heating
... ...
Supply air type Control Manually
Max. supply air temp. manually 40 °C
Max. Supply air temperature
Auto
This parameter enables the user to set the maximum supply air temperature individually.
The maximum supply air temperature must be increased step by step in winter (depending on outdoor temperature).
Automatic setting
max. supply air temperature automatically
Setpoint at (-15) 48 °C
Setpoint at (-5) 44 °C
Setpoint at (5) 40 °C
Setpoint at (15) 36 °C
Parallel offset 0 °C
TIP
The higher the efciency standard of the house, the lower the values can be set.
Manual operation (default setting 40°C) may be appropriate, depending on user behaviour.
Offset(thetemperaturecurve)
Offset
Adjustment range: -5 °C ... +5 °C
Default setting: 0 °C
- Heat pump start
Start hyst.: HP starts with a request 30 % " The value is not adjustable.
- Start/Stop hyst.
Start hyst. 0.3 °C
Stop hyst. 0.4 °C
Start/Stop hyst. This parameter prevents heat pump cycles and enables longer operation and longer
standstill times. This extends the unit lifetime.
Default setting: 0.3 °C, 0.4 °C
The factory settings can be changed. A
value of 0.2 °C should not be undershot.
The hysteresis is visibly taken into account on the setpoint.
Setpoint temperature (+Hyst.) 21.3 °C
Setpoint room heating 21.0 °C
71
Genius - V 1.0
Operation/Control via Internet/App