Installation , Operation and Maintenance Instructions Genius
Room setpoint depending on outdoor temperature
A gradual increase of the setpoint temperature with decreasing outdoor temperature compensates the inuence of the lower surface
temperatures of room walls and windows to comfort.
Setpoint heating curve
Setpoint at (-15) 23 °C
Setpoint at (-5) 22 °C
Setpoint at (5) 21 °C
Setpoint at (15) 20 °C
Offset value -1 °C
Offset(thetemperaturecurve)
Offset The curve will be displayed on the Actual Value/Setpoint page. Offset manually from
-3 °C up to +3 °C.
Example: The average room temperature setpoint changes from 21 °C to 20 °C with
an offset of -1 °C.
The curve values remain below Actual setpoint/Setpoint constant also after an
offset. The room setpoint changes visibly.
Adjustment range: -3 °C ... +3 °C
Default setting: 0 °C
Heating: Setback temperature
Setback temperature This parameter denes the room temperature setpoint decrease during offset in
heating mode (see „10.7.2 Time Program“ page 60).
Example:
Setpoint temperature 21 °C
Night setback 2 °C
(Setback) Setpoint temperature 19 °C
Adjustment range: 0 °C ... 10 °C
Default setting: 0 °C
Heating
... ...
Night setback room difference 2 °C
NOTE
A night setback can be recommended for the Outdoor compensated room setpoint offset, because an automatic set-
point increase can be avoided or compensated.
Heating: Holiday program
Holiday program The average room temperature will be maintained to the setpoint value during the
holiday program (see Time Program).
Adjustment range: 16 °C ... 20 °C
Default setting: 18 °C
Heating
... ...
Temperature holiday mode 18 °C
TIP
Do not regulate the residential unit temperature below 18 °C due to energetic reasons.
68
Operation/Control via Internet/App
Genius - V 1.0