Installation , Operation and Maintenance Instructions Genius

Setpoint cooling curve
Room setpoint at (32) 26 °C
Room setpoint at (30) 25 °C
Room setpoint at (28) 24 °C
Room setpoint at (26) 23 °C
Offset (-3 up to +3) 0 °C
Setpoint value temperature 26 °C
Offset value 0 °C
Offset value -1 °C
Setpoint value temperature 25 °C
Room setpoint depending on outdoor temperature
Room setpoint depending on actual outdoor temperature
Start outdoor temp. Room setpoint at 26 °C 28 °C 30 °C 32 °C
26* °C 23 24 25 26
* Outdoor temp. 26 °C = start point cooling, basic setting
Offset(thetemperaturecurve)
Offset The curve (see above) will be displayed on the Actual Value/Setpoint page. An offset
is possible there.
Example: The average room temperature setpoint changes from 25 °C to 24 °C with
an outdoor temperature of 30 °C and an offset of -1 °C.
The curve values of the outdoor temperature remain below Actual setpoint/setpoint
constant also after an offset. The room setpoint changes visibly.
Adjustment range: -3 °C ... +3 °C
Default setting: 0 °C
Room setpoint as a xed value
Room setpoint After selecting this parameter, the value appears 26°C below the Actual value/set-
point, Unit, Room setpoint cooling.
Adjustment range: 22 °C - 28 °C
Factory settings Room setpoint cooling
26 °C
Unit
Status . tion. tion.
tion. tion. tion. tion. tion. tion.
Room setpoint cooling 26.0 °C
66
Operation/Control via Internet/App
Genius - V 1.0