Installation , Operation and Maintenance Instructions Genius

10.8.1.1 Operation Mode
Heating/Cooling Auto
Cooling active when outdoor temp. > Winter operation
Heating active when outdoor temp. < Summer opera-
tion
Heating/Cooling
Cooling active when outdoor temp. > 26 °C
Heating active when outdoor temp. < 20 °C
Heating/Cooling
Settings: Winter operation, Summer
operation and Automatic
Factory settings and recommendation:
Auto(matic operation).
Cooling active when outdoor temp. > 26 °C
Heating active when outdoor temp. < 18 °C
Automatic operation:
Active heating and cooling function
The (active) heating and cooling function of the heat pump is switched off between
these two temperature values. The (passive) heat or cooling recovery by the rotating
heat exchanger is maintained. These values are adjustable. For further information
about individual settings, see „13 Comfort and Energy Efciency page 100.
Within this neutral zone (20 ... 26°C) the unit remains in Heating mode with the cor-
responding setpoint values .
Adjustment range:
Heating: 10 ... 23°C, cooling: 23 ... 34°C
Factory settings outdoor temperature:
18°C and 26°C.
Cooling: Type of the room temperature controlled control
Control mode An individual room temperature control is not possible during cooling mode. The
setpoint is dened as an average room temperature. It is either depending on the
outdoor temperature (Outdoortemp.comp.) or determined by a Fixed value. The
associated value is the average room temperature of all rooms. Depending on choice,
the values will be displayed on page Actual/Setpoint.
Settings: Outdoortemp.comp. / Fixed
value
Default setting: Outdoortemp. managed
NOTE
The setpoints of the room controllers are not relevant in the cooling mode. However, they are automatically increased
as soon as the cooling mode is active.
Cooling
Room temperature value Outdoortemp.comp.
Outdoortemp.
comp.
Fixed setp.
Outdoortemp.comp.
65
Genius - V 1.0