Installation , Operation and Maintenance Instructions Genius

Figure 25: Page Settings 2
10.8.1 Room Temperature Control
Room temperature control
Heating/Cooling Auto
Cooling active when outdoor temp. > 26 °C
Heating active when outdoor temp. < 20 °C
Cooling
Control mode Outdoortemp. managed
Heating
Control mode Fixed setp.
Reference room 1
Setback operation room difference 0 °C
Temperature holiday mode 18 °C
Temperature rotor alarm 19 °C
Control parameters
Room controller
Actual value 21.7 °C
Setpoint 21.8 °C
Control output 43 °C
P-band 3 °C
I-time 20 s
Sup.air temp.con
Actual value 32.3 °C
Setpoint 42.6 °C
Control output 100 %
P-band 70 °C
I-time 30 s
min. supply air temp. 16.5 °C
Supply air control type Automatic
Max. Sup.air temp.man. 40.0 °C
Max. Sup.air temp.auto
Setpoint at (-15) 48 °C
Setpoint at (-5) 44 °C
Setpoint at (5) 40 °C
Setpoint at (15) 36 °C
Offset (-5 up to +5) 0 °C
HP starts with a request > 30 %
Start hyst. 0.3 °C
Stop hyst. 0.4 °C
64
Operation/Control via Internet/App
Genius - V 1.0