Installation , Operation and Maintenance Instructions Genius

10.8 Settings
Genius
Room temperature control Heat pump
Heating/Cooling Auto ModBus address 1
Cooling active when outdoor
temp. >
26 °C Activate supply air rooms
Heating active when outdoor
temp. <
20 °C Number of rooms 6
Cooling Room 1
Control mode Outdoortemp.comp. Modbus room address (ELA) 197
Heating Room 2
Control mode Fixed setp.
Modbus room address (ELA) 39
Reference room 3 Room 3
Night setback room difference 0 °C Modbus room address (ELA) 147
Temperature holiday mode 18 °C Room 4
Temperature rotor alarm 19 °C Modbus room address (ELA) 82
Control parameters Room 5
Room controller Modbus room address (ELA) 237
Actual value 21.7 °C Room 6
Setpoint 21.8 °C Modbus room address (ELA) 200
Control output 43 °C Default settings rooms
P-band 3 °C Room 1
I-time 20 s Room sensor internal
Sup.air temp.con Setpoint room temperature 20.0 °C
Actual value 37.3 °C Temperature rise + 3 °C
Setpoint 42.6 °C Temperature setback - 3 °C
Control output 100 % P-band 3 °C
P-band 20 °C I-time 20 s
I-time 100 s Room designation Living room
min. supply air temp. 16.5 °C Room 2
Supply air control type Automatic Room sensor internal
Max. Sup.air temp.man. 40.0 °C Setpoint room temperature 20.0 °C
Max. Sup.air temp.auto Temperature rise + 3 °C
Setpoint at (-15) 48 °C Temperature setback - 3 °C
Setpoint at (-5) 44 °C P-band 3 °C
Setpoint at (5) 40 °C
I-time 20 s
Room designation Bedroom
Figure 24: Page Settings 1
62
Operation/Control via Internet/App
Genius - V 1.0