Installation , Operation and Maintenance Instructions Genius
10.6 Input/Output
Genius
Heat pump Analogue inputs
Status On AE1, outdoor temperature 7.1 °C
Heating/Cooling Heating AE2, supply air temperature 23.4 °C
Capacity requirement 90 % AE 4, extract air temperature 22.0 °C
Defrost Off UAE1, hot water temperature 44.6 °C
Temp. air heat exchanger 21.1 °C UAE2, Supply air fan monitoring 10 V
Temp. suction gas 21.6 °C UAE3, Extract air fan monitoring 10 V
Cond. Temp. 22.0 °C UAE4, Secondary air fan monitoring 10 V
Temp. hot gas 27.0 °C Digital inputs
Zone hot gas 90.0 °C DE1, EVU status On
Status hot gas OK DE2, Pressure monitoring alarm Off
Cond. pressure 14.2 bar DE3, PV Off
Evaporator pressure 14.1 bar DE4, Rotor operation On
Differential pressure 0.1 bar Analogue outputs
Requested capacity comp. 0 % AA1, supply air fan control 6.0 V
Actual capacity comp. 0 % AA2, extract air fan control 5.5 V
Actual speed comp. 0 U/s AA3, secondary air fan control 0.0 V
Status envelope curve 27 AA4, Preheater. 0.0 V
Alarm countdown 180 s Digital outputs
Pressure ratio 1 DA1, Off
Low pressure countdown 60 s DA2, Off
Extern. Fan 0 % DA3, Off
Compressor Off DA4, rotor On/Off On
4-way valve On DA5, sum alarm Off
Overheating 5 K DA6, storage charge pump Off
Valve status 3 DA7, heating rod HW Off
Valve status 0 stp
Valve status 0 %
Figure 22: Page Input/Output
10.6.1 Heat Pump
You can read the most important actual heat pump status. This is very useful during an error analysis. The parameters of the cooling cir-
cuit can only be read and if possible adjusted with the external control, see „9.3.1 External Heat Pump Control“ page 46.
56