Installation , Operation and Maintenance Instructions Genius
Unit
Status Hot water gen-
eration
Ventilation day-time operation normal
Ventilation setback operation Humidity pro-
tection
Actual ventilation stage Minimal
Actual room temperature normal
Setpoint value temperature Party
Setpoint supply air temperature Off
Humidity protection Use the function Humidity protection only in case of longer absence (see Time pro-
gram/Holiday).
WARNING
Building fabric humidity protection!
" Do no use during long absence and high humidity load (e.g. plants) the ventilation for humidity protection, use
the next higher stage.
Reduced ventilation stage Use this function in case of longer absence, optionally in the night.
Intensive ventilation (party mode) This function temporarily discharges peak loads. This function is reset automatically
after one hour.
Off Switching off must be ensured for safety reasons. It can be used for manual ventila-
tion (e.g. summer).
10.4.1.3 Setpoint Temperature Display
Shows the actual (room) temperature after which the unit is controlled for both heating and cooling operation. In the factory settings,
the control system is set to a xed value for heating. For cooling the value is dependent on the external temperature. In this setting, the
values are visible as curves, or otherwise as the relevant mode for heating or cooling (see „10.8 Settings“ page 62).
Actual room temperature 21.4 °C
Setpoint value temperature 21.5 °C
Setpoint heating curve
Room setpoint at (-15) 23 °C
Room setpoint at (-5) 22 °C
Room setpoint at (5) 21 °C
Room setpoint at (15) 20 °C
Offset (-3 up to +3) 1 °C
Setpoint cooling curve
Room setpoint at (32) 26 °C
Room setpoint at (30) 25 °C
Room setpoint at (28) 24 °C
Room setpoint at (26) 23 °C
Offset (-3 up to +3) 0 °C
52
Operation/Control via Internet/App
Genius - V 1.0