Installation , Operation and Maintenance Instructions Genius

9.2.7 SacricialAnode
To replace the sacricial anode, the heat pump module must be removed and the water must be drained from the tank by one third.
Pull out the heat pump module
" Loosen the two inlet and outlet nozzles on the rear side of the unit.
" Depressurize the connection pipes.
" Disconnect the two connections below the heat pump module.
" Disconnect the plug below the heat pump module on the left side.
" Disconnect the expansion valve plug connection on the board. For precise information please refer to the electric wiring diagram in
the appendix.
" Loosen screws M6 on the front of the left and right guide rails with an allen key.
» The support of the heat pump module is lowered by approx. 1.5 cm.
" Pull out the lowered module.
Drain water
" Close the cold water supply.
" Connect a hose to the drain valve.
" Open a water tapping point during the drain procedure to prevent negative pressure.
" Drain the water of the tank by one third (about 50 litres).
Changesacricialanode
" Unscrew the sacricial anode an replace it by a new one.
" Install the heat pump module in reverse order.
" Fill the tank completely.
9.2.8 Electric Heating Rod
The hydraulic circuit is equipped with an electric heating rod of 3 kW. To protect the heating element against overheating, a safety tem-
perature limiter (STL) is mounted on the component. Tripping of the STL interrupts the power supply and cuts off the electric heating rod.
Check
" The STL has triggered when the black splint pin of the STL sticks out.
Suppression
" Push the splint pin in to clear the STL fault.
NOTE
More detailed information about the electrical wiring, refer to the wiring diagram chapter „16 Appendix page 106.
45
Genius - V 1.0
Service