Installation , Operation and Maintenance Instructions Genius
8.2.1.1 Change Filter
(see „Figure 12: Change lter“)
WARNING
Danger of injury from rotating fans!
Rotating fans can cause very severe injuries.
» Disconnected the unit completely from the power supply before opening!
9 Precondition: The combi unit is disconnected from the power supply.
" Open the shutter of the ventilation module.
" Pull out the lters 1, 2 and 3.
" Insert the new lter.
NOTE
Respect the air ow direction (arrow on the lter).
" Always check the rotating heat exchanger for contamination (dust) during lter change.
8.2.1.2 Check and Clean Rotating Heat Exchanger
1
Legend
1 Heat exchanger unit
Figure 13: Check and clean rotating heat exchanger
9 Precondition: The combi unit is disconnected from the power supply.
" Disconnect the two plugs of the rotor unit.
" Pull out the complete heat exchanger unit.
WARNING
Danger electrical voltage!
Humidity inside the drive motor of the heat exchanger can cause a short circuit.
» Do not expose the drive motor to humidity!
" Blow the heat exchanger out or rinse it with hot mild suds.
" Do not use any cleaning detergents.
" Insert the heat exchanger unit.
" Connect the two plugs.
" Close the cover.
" Connect the Combi Unit Genius to the electrical power supply.
38
Maintenance / Remedying Faults