Installation , Operation and Maintenance Instructions Genius
1 Air vent storage charging circuit
2 Fill and drain valve with ½“ hose connection
Figure 9: Fill and vent storage charging circuit
Fill and vent storage charging circuit
Recommended unit pressure: 1.5 bar
" Unscrew the left cover of the heat pump module.
" Remove the cover forward.
" Activate the vent valve of the heat pump module (1).
" Connect the ll and drain valve (3) with a hose to the water network.
" Open the ll and drain valve and ush the hydraulic circuit bubble-free.
7.2.4 Fill the Tank for the Hydraulic Seal
" Fill the collection tank for the condensate hoses with a
hydraulic seal.
Figure 10: Fill the collection tank
7.2.5 Start Unit
The unit can be started after installation and commissioning of the combi unit.
" Mount and screw all panels.
" Start the unit.
26
Commissioning
Genius - V 1.0