Unit Data
Performance data
max. heating capacity kW 6
max. cooling capacity kW 4
Power PTC elements (Accessories) W each 500
Power heating rod kW 3
Coefcient of performance for A7/L40 3.3
Coefcient of performance for A2/L40 2.9
Coefcient of performance for A-7/L40 2.3
Electrical data
Max. power input supply and extract air fan W 80 (standard version)
170 (version L)
Max. power input secondary air fan W 170
Max. input power compressor W 1800
max. power input fans module ventilation W each 80
max. power input fan module heat pump W 170
Power input storage charge pump W 6 ... 28
Supply voltage V 230
Frequency Hz 50
Protection class IPX2
Ventilation
Filter class outdoor air F7
Filter class extract air G4
Filter class secondary air G4
Air ow rate (standard operation) m³/h 180 (standard version)
230 (version L)
max. air ow heating/cooling (secondary air) m³/h 550 (standard version)
600 (version L)
Fresh air heat recovery % up to 85
Dimensions / Weight
Width mm 865
Height mm 2070
Depth mm 750
Weight ventilation module kg 75
Weight heat pump module kg 60
Weight basic module/hot water kg 170
Total weight, empty kg 305
Total weight, lled kg 460
Fittings
Table 1: Technical Data combi unit Genius