DATASHEET AES ST32

Table Of Contents
Top view controlboard AES-ST3.2
Function OnBoard-Diagnose and control elements:
system ready
system in smoke extraction
system fault is present, staked adjustment module (AES BTxS) or see ads of OB diagnostics
indicator GREEN:
RED:
OUT:
system OFF, by FWS "OFF" or input "Look"
triggering in maintained command
indicator YELLOW:
RED:
input "repair switch" open or fuse (F1, F2) dropped
no fault
indicator YELLOW:
OUT:
wire break or short circuit of the displayed detector loop
triggering active
detector circuit without fault, no tripping
indicator YELLOW:
RED:
OUT:
motor protection triggered or input "motor protection" open message maintained command
no fault
after checking and resetting the ext. surveillance authority
press button to reset message
indicator YELLOW:
OUT:
Button „reset“:
triggering on the BMZ is not maintained command
triggering on the BMZ is maintained command
Switch ON:
OFF:
detector circuit for latching manual call via NC
detector circuit for smoke vent button (HRM-3)
Switch DKM:
HRM:
(wire break = release)
(wire break = fault)
output voltage determined in smoke extraction operation 10V
output voltage in smoke extraction operation the same as for ventilation level 2
Switch 10V:
St.2:
setting output voltage 0-5V for ventilation level 1
setting output voltage 5-10V for ventilation level 2 (and smoke extraction operation)
rotarypoti St.1:
St.2:
Settings for analog output at terminal 25:26
Reset saved trips
press: tripping on hand detector and BMZ is reset. Only possible if no trigger is present.
1sec to press: triggering the automatic RM will reset and the detector circuit for 3sec interrupted
3sec to press: triggering at FWS is reset. Only possible if previously FWS "Off"
Function is the same as using button "Sys Reset".
Button:
Input terminal 60:61:
power supply
-F1
-F2
release
flap
ventilation
stage 2
signal
fail
smoke extraction
ventilation
stage 1
signal
smoke extraction
HRM
HRM
HRM
HRM
ARM
ARM
11.15
D
Edition Version